Troubleshooting using the IO Controller indicators
Unit number duplication
CPU Unit fault
Backplane bus error
82
7-segment
H1
7-segment
H6
7-segment
H7
MS indicator
Flashing (red)
MS indicator
Flashing (red)
MS indicator
Flashing (red)
/i
Likely cause
At startup the PROFINET lO Controller detected that there is another Unit
having the same Unit number set.
IO Controller Unit response
The Unit will stop processing.
CIO Area Flags allocated to the IO Controller Unit
None of the bits is set.
Correction
Correct the Unit number of the IO Controller or the other Unit. Restart the PLC.
/i
Likely cause
The PROFINET lO Controller detected that PLC CPU Unit is faulty.
IO Controller Unit response
The Unit will stop processing.
CIO Area Flags allocated to the IO Controller Unit
None of the bits is set.
Correction
Replace the CPU Unit if the error recurs when the CPU Unit is restarted.
/i
Likely cause
The PROFINET lO Controller detected that an error on the backplane bus.
IO Controller Unit response
The Unit will stop processing. Records the error in the error log. (The time
information is set to all zeroes.)
CIO Area Flags allocated to the IO Controller Unit
None of the bits is set.
Correction
Replace the CPU Unit if the error recurs when the CPU Unit is restarted.
NS indicator
OFF
NS indicator
OFF
NS indicator
OFF
Error log (Hex)
--
Error log (Hex)
--
Error log (Hex)
--
Section 6-2