CJ1W-PNT21 Omron, CJ1W-PNT21 Datasheet - Page 47

no-image

CJ1W-PNT21

Manufacturer Part Number
CJ1W-PNT21
Description
CJ Profinet Master
Manufacturer
Omron
Datasheet

Specifications of CJ1W-PNT21

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
CX-ConfiguratorFDT
4-1
34
CX-ConfiguratorFDT
Omron CX-ConfiguratorFDT is the versatile network configuration tool for
networks such as PROFIBUS and PROFINET. It is based on FDT/DTM
technology. CX-ConfiguratorFDT is Omron’s standalone FDT-container. For
the various networks Omron provides device specific DTM’s.
To configure PROFINET Omron delivers three different DTM’s:
This section provides information about the use of the CJ1W-PNT21
PROFINET IO Controller DTM and the Generic IO Device DTM. For the use of
the GRT1-PNT SmartSlice PROFINET IO Device DTM please refer to the
manual of the GRT1-PNT PROFINET IO Communication Unit (W13E-EN).
CJ1W-PNT21 PROFINET IO Controller DTM.
This DTM is used to configure the IO-Controller to perform data-exchange
and to set up the memory locations for the I/O data-exchange.
Furthermore, the DTM provides online diagnostics functions.
GRT1-PNT SmartSlice PROFINET IO Device DTM.
This DTM is used to configure the GRT1-PNT SmartSlice system. The type
and number of units inserted in the SmartSlice system can be configured.
This defines the amount of I/O data that is exchanged with the PROFINET
IO Controller. All parameters of the SmartSlice buscoupler and the
separate SmartSlice units are directly accessible.
Generic IO Device DTM.
This DTM interprets standard PROFINET IO GSDML files. The DTM can
only be used to configure the I/O Data exchange between the PROFINET
IO Controller and PROFINET IO Devices. The DTM only contains very
limited online diagnostics functions and online parameter setup is not
possible.
Section 4-1