Troubleshooting using the IO Controller indicators
6-2-3-1 Unit errors
Startup errors
6-2-3-2 IO Controller Functions
PROFINET configuration
set invalid
IO Controller
function
PROFINET
Network errors
Memory access
errors
CPU Unit
Exchange
7-segment
1 to 6
7-segment
C7
Error category
PROFINET configuration set invalid
Ethernet failure
Bus hardware error
Special Unit error
Memory access error
Backplane bus error
Unit number duplication
CPU Unit faulty
I/O table not registered
CPU Unit service monitoring error
CPU Unit watchdog timer error
Note
MS indicator
ON (red)
MS indicator
ON (green)
Error
If Module Status is Red lit or flashing then refer to the displayed error code on the 7-
segment display for further information.
/i
Likely cause
During startup of the IO Controller it encountured a problem and can not
continue
IO Controller Unit response
The Unit will stop processing. There will be no error logged in the errorlog.
CIO Area Flags allocated to the IO Controller Unit
None of the bits is set.
Correction
Restart the IO Controller. Replace the IO-Controller if the error recurs.
/i
Likely cause
During startup of the IO Controller encountered a problem interpreting the
PROFINET IO Configuration file. This could be because the Unit started for
the first time
Configuartion file could have been damaged.
and does not contain a configuration file yet. Also the
NS indicator
OFF
NS indicator
Flashing (red)
C7
E3
E5
--
E9
H0
H1
H6
H7
HE
HF
7-segment
ON (green) Flashing
ON (red)
ON (red)
Flashing
(red)
Indicators
MS
Error log (Hex)
--
Error log (Hex)
0202
(red)
OFF
OFF
OFF
NS
0202
020C
0219
0601
0602
000E
--
--
--
0001
0002
Error log
(Hex)
Section 6-2
79