CJ1W-PNT21 Omron, CJ1W-PNT21 Datasheet - Page 80

no-image

CJ1W-PNT21

Manufacturer Part Number
CJ1W-PNT21
Description
CJ Profinet Master
Manufacturer
Omron
Datasheet

Specifications of CJ1W-PNT21

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Allocated CIO Area Words
Bit
01~07
08
09~11
12
13~15
Name
Reserved
Clear all alarm bits
Reserved
Set Output Data Valid
(See Note)
Reserved
Note
/i
The Set Output Data Valid switch controls the Provider Status in the Output Data sent
from the IO Controller to the IO Device. If the IO Device is receiving Output Data with
the Provider Status bit set to invalid then the IO device will discard the Output Data.
The Provider Status can be used in a redundant IO Controller setup where the Active IO
Controller sents it Output Data with the Provider Status set to valid. The other IO Con-
troller is then in Standby mode and has its Provider Status set to invalid.
To change from Active to Standby and vice versa only the Set Output Data Valid switch
must be set or reset. The IO Device will only use the output data that is valid.
As there is no need to first open connections and sent configurations as this already
has been done this changeover is very fast.
When the Output Data Valid flag is PLC mode dependent, the Output Data Valid flag in
this word will be ignored.
For more information see Appendix A PROFINET IO technology.
Status
---
The clear alarm bits switch will clear all alarm flags for all IODs. It is rising
edge triggered. The unit will set the switch to OFF when all alarm flags are
cleared.
OFF --> ON
ON --> OFF
---
OFF
ON
---
Unit operation
These bits are ignored in the unit. If set, they will be
turned OFF by the Unit the next PLC cycle.
Clear alarm bits for all IODs.
No action.
These bits are ignored in the unit. If set, they will be
turned OFF by the Unit the next PLC cycle.
Mark all output data sent by the IO Controller as
invalid. IO Devices will ignore the data.
Mark all output data send by the IO Controller as
valid. IO Devices will accept the data and process it.
These bits are ignored in the unit. If set, they will be
turned OFF by the Unit the next PLC cycle.
Section 5-2
67