CJ1W-PNT21 PROFINET IO Controller DTM
Search Devices Button
46
To populate the Network Scan View follow the next sequence:
1 Press the Search Devices button to scan the network and get an overview
2 Locate the IO devices at their physical location by making the IO
3 Give each IO Device its PROFINET IO Device name.
The Controls have the following function:
/i
Search Devices
Signal
Set IP Address
of all the PROFINET devices connected to the Ethernet network.
Controllers and IO Devices flash their LED’s.
Control
The Search Devices button initiates a scan of the network
and shows all found PROFINET IO Devices in the Network
Scan View. For each device the MAC Address, Device Type,
the currently assigned name and IP Address are displayed.
The PROFINET Name and the IP Address can be adjusted
from within this view.
When selecting “Signal” the selected IO Device or IO Con-
trollers will flash its LEDs for 3 seconds. This can be used to
locate the IO Controller or IO Device.
An IP Address can be temporarily set to access the IO
Device over TCP/IP with a device-specific tool. When the IO
Controller opens a connection to the IO Device the IP
Address is overwritten by the IP Address set in the IO Con-
troller’s configuration file.
The IP Address can also be set temporarily for the IO Con-
troller, however this can only be done when there is no con-
figuration file in the IO Controller.
Figure 4.7: Network scan
Description
Section 4-3