E8MS-N0 Omron, E8MS-N0 Datasheet - Page 19

SENSOR PRESSURE NEGATIV 0-101KPA

E8MS-N0

Manufacturer Part Number
E8MS-N0
Description
SENSOR PRESSURE NEGATIV 0-101KPA
Manufacturer
Omron
Series
E8MSr
Datasheets

Specifications of E8MS-N0

Pressure Type
Gauge
Operating Pressure
-14.65 ~ +0 PSI, -101 ~ 0 kPa
Port Size
Male, 1/8" (3.175mm) 27 NPT
Output
Digital
Voltage - Supply
12 V ~ 24 V
Termination Style
Cable
Operating Temperature
0°C ~ 50°C
Package / Case
Module
Sensor Output
Voltage
Supply Current
25mA
Voltage Rating
12V
Port Style
NPT, M5
Pressure Measurement Type
Gage
Operating Pressure Min
0psi
Terminal Type
Connector
Operating Pressure Max
14.6psi
Mounting Style
Desktop
Maximum Operating Temperature
+ 50 C
Minimum Operating Temperature
0 C
Operating Supply Voltage
12 V
Output Voltage
1 V to 5 V
Pressure Port
Y
Sensor Type
Sensors
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Lead Free Status / RoHS Status
Lead free / RoHS Compliant, Lead free / RoHS Compliant
Other names
E8MSN0
One-point Teaching (Window Mode Teaching)
1. By pressing the TEACH Key at the point of status 3 as shown below, the present measurement value will appear and ON- and OFF-
2. Check the measurement value and press the TEACH Key for teaching. Teaching will be completed on the ON and OFF points.
3. Press the RST/ESC Key so that the Controller will be in measurement mode.
Note: The Controller will be in window mode automatically after one-point teaching.
The above settings are useful for applications that check original pressures.
ON- and OFF-point Set Values
Refer to Set Value Check on page 17 to check ON- and OFF-point set values.
Teaching Errors
Teaching will not be performed by pressing the TEACH Key if the present value or the result of teaching is not within the proper setting
range, in which case, “ER.T” (error teach) will appear for 1 s.
Measurement Value Zero-reset
Note: The Controller can be zero-reset provided that the Sensor is exposed to atmospheric pressure.
The present measurement value will be reset as zero by pressing the RST/ESC Key for 1 s. The possible zero-reset range is within ±5%
FS of the rated output. Otherwise, “ER.T” will appear and the present measurement value will not be reset.
E8M/E8MS
The present value is not within
the proper setting range.
point indicators will start flashing.
One-point Teaching
ON point = Teach 1 - - 30% FS
OFF point = Teach 1 + 30% FS
Default is 10% FS (can be changed).
ON point OFF point
ON-point and
OFF-point indicators
flash.
Press the RST/ESC
Key for 1 s.
Status 3
Pressure
Present
measurement
value appears.
“ER.T” (error teach)
appears for 1 s.
Teaching completed.
20
Measurement mode
E8M/E8MS