CS1W-CN224 Omron, CS1W-CN224 Datasheet - Page 116

no-image

CS1W-CN224

Manufacturer Part Number
CS1W-CN224
Description
"CABLE,CS1/C200H PRO27,2m"
Manufacturer
Omron
Datasheets

Specifications of CS1W-CN224

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
I/O Link Unit for C200H# and CS1 PLC
Ideal for distributed control.
• OMRON’s C200HS, C200HE, C200HG, C200HX
• Default 2 words in + 2 words out, maximum
• Simple PROFIBUS-DP node address setting by
• Supports SYNC/FREEZE and Fail-Safe functions.
Communication Specifications
Unit Specifications
362
Applicable standard
Station type
Bus connector
Bus termination
Baud rate (auto-detect)
PROFIBUS address range
Communication cable
Minimum slave interval time
Supported DP functions
PROFIBUS-DP GSD file
Host PLC system
Maximum number of Units per PLC system
Slave unit mounting position
Current consumption
Weight
Switch settings
LED indicators
No. of IR words
No. of DM settings
Amount of I/O data per Unit
Storage temperature
Operating temperature
Operating humidity
Conformance to EMC- and environmental standards EN50081-2
Specifications
C200HW-PRT21
PROFIBUS-DP Slave Unit
and CS1 PLCs can be used as an intelligent Slave
on a PROFIBUS-DP network.
100 words in + 100 words out.
rotary switches.
EN 50170 vol. 2
Modular station, max. 32 modules
Configurable with In-, Out- and I/O-modules of 1, 2, 4, 8 and 16 words
Total of 0 to 100 words in + 0 to 100 words out, with consistency over the full length
9-pin female sub-D connector (RS-485 PROFIBUS connector)
External
9.6 / 19.2 / 45.45 / 93.75 / 187.5 / 500 kbit/s,
1.5 / 3 / 6 / 12 Mbit/s
0 to 125, Remote setting not supported
Type A (EN 50170 vol. 2)
0.5 ms
OC_04AC.GSD
C200HS, C200HE, C200HG, C200HX, CS1
C200HS
C200HE-CPU11/32/42
C200HG-CPU33/43
C200HX-CPU34/44
All others
CPU Rack or Expansion I/O Rack
Unit: cannot be mounted to SYSMAC BUS Slave Racks
Unit: cannot be used on a C200H PLC system
250 mA at 5 V DC (from PLC power supply)
180 g
Special I/O Unit number (0-F) by notary switch
PROFIBUS-DP mode address (o to 125) by 3 rotary switches
Unit status:
Network status:
PLC to Slave Unit: 3 words (1 word of control data + 2 words slave input data)
Slave unit to PLC: 5 words (3 words of unit status + 2 words slave output data)
8 words of Unit setup information
Default (DM settings all 0000)
With user defined DM settings
- 20 °C to + 75 °C
0 °C to + 55 °C
10% to 90% (non-condensing)
EN61131-2
Data_Exchange
Slave_Diag
Set_Prm
Chk_Cfg
Global_Control (SYNC, FREEZE, CLEAR)
Get_Cfg
RD_Imp
RD_Outp
RUN (green LED), ERR (red LED)
COMM (green LED), BF (red LED)
10
16
all PLC’s: 2 words in + 2 words out
C200HS: up to 80 words in + out
all others: up to 100 words in + 100 words out
Programmable Controllers