CS1W-CN224 Omron, CS1W-CN224 Datasheet - Page 31

no-image

CS1W-CN224

Manufacturer Part Number
CS1W-CN224
Description
"CABLE,CS1/C200H PRO27,2m"
Manufacturer
Omron
Datasheets

Specifications of CS1W-CN224

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Function Specifications
CS1-series
Item
Parallel Processing Mode
Battery-free operation
Constant cycle time
Cycle time monitoring
I/O refreshing
I/O memory holding when changing oper-
ating modes
Load OFF
Input time constant setting
Mode setting at power-up
Memory Card functions
Filing
Debugging
Online editing
Program protection
Error check
Error log
Serial communications
Clock
Power OFF detection time
Power OFF detection delay time
Memory protection
Sending commands to a Host Link
computer
Remote programming and monitoring
Eight-level communications
(CPU Ver. 3.0 and higher)
Storing comments in CPU Unit
Program check
Control output signals
Battery life
Self-diagnostics
Other functions
Specification
The program can be executed simultaneously with peripheral servicing (CS1G/CS1H only).
Flash memory is provided as a standard feature and automatically backs up the user program and system parameters.
1 to 32,000 ms (Unit: 1 ms)
Possible (Unit stops operating if cycle is too long): 1 to 40,000 ms (Unit: 10 ms)
Cyclic refreshing, immediate refreshing, refreshing by IORF(097).
Possible (Depends on ON/OFF status of IOM Hold Bit in Auxiliary Area.)
All outputs on Output Units can be turned OFF.
Time constants can be set for inputs from CS1 Basic I/O Units. The time constant can be increased to reduce influence of
noise and chattering or it can be decreased to detect shorter pulses on inputs. (CS1 Basic I/O Units only)
Possible
Automatic reading programs from Memory Card (autoboot).
Memory Card Storage Data
User program: Program file format (binary)
PC System Setup: Data file format (binary)
I/O Memory: Data file format (binary), text format, CSV format
Memory Card Read/Write
User program instructions, Peripheral Devices (such as Programming Console), Host Link computer.
Memory Card data and EM (Extended Data Memory) Area can be handled as files.
Force-set/reset, differential monitoring, data tracing (scheduled, each cycle, or when instruction is executed), instruction error
tracing.
One or more program blocks in user programs can be overwritten when CPU Unit is in PROGRAM or MONITOR mode.
This function is not available for block programming areas.
Overwrite protection:Set using DIP switch.
Copy protection: Password set using Peripheral Device.
User-defined errors (i.e., user can define fatal errors and non-fatal errors)
The FPD(269) instruction can be used to check execution time and logic of each programming block.
Up to 20 errors are stored in error log. Information includes error code, error details, and time error occurred.
Built-in peripheral port: Peripheral Device (including Programming Console), Host Links, NT Links
Built-in RS-232C port: Peripheral Device (excluding Programming Console), Host Links, no-protocol communications,
NT Links
Communications Board (sold separately): Protocol macros, Host Links, NT Links
Provided on all models.
Note: Used to store time when power is turned ON and when errors occur.
10 to 25 ms (not fixed)
0 to 10 ms (user-defined, default: 0 ms)
Held Areas: Holding bits, contents of Data Memory and Extended Data Memory, and status of counter Completion Flags and
present values.
Note: If IOM Hold Bit in Auxiliary Area is turned ON, and PC Setup is set to maintain IOM Hold Bit status when power to
FINS commands can be sent to a computer connected via Host Link System by executing Network Communications
Instructions from PLC.
Host Link communications can be used for remote programming and remote monitoring through a Controller Link System or
Ethernet network.
Host Link communications can be used for remote programming and remote monitoring from devices on networks up to
seven levels away (Controller Link Network, Ethernet Network, or other network).
I/O comments can be stored in CPU Unit in Memory Cards, EM file memory, or the built-in Comment memory
(CPU Ver. 3.0 and higher)
Program checks are performed at beginning of operation for items such as no END instruction and instruction errors.
A Peripheral Device (excluding Programming Console) can also be used to check programs.
RUN output: The contacts will turn ON (close) while CPU Unit is operating. These terminals are provided only on C200HW-
PA204R and C200HW-PA209R Power Supply Units.
5 years at 25 C (Depending on the ambient operating temperature and communications conditions, 1.1 years min. Battery
Set: CS1W-BAT01)
Note: Use a replacement battery that is no more than 2 years old from the date of manufacture.
CPU errors (watchdog timer), I/O verification errors, I/O bus errors, memory errors, and battery errors.
Storage of number of times power has been interrupted, the times of the interrupts, and system operation time (in Auxiliary
Area).
PLC is turnedl ON, contents of CIO Area, Work Area, part of Auxiliary Area, timer Completion Flag and PVs, Index
Registers, and Data Registers will be saved.
277