Note: Refer to pages 318 to 322 for descriptions of the Analog I/O Units (CS1W-AD0@@, CS1W-DA0@@, CS1W-MAD44.)
Process I/O Units
Unit name
Isolated-type
Thermocouple
Input Unit
Isolated-type
Resistance
Thermometer Input Unit
Isolated-type
Thermocouple
Input Units
(Economical type)
Isolated-type
Resistance
Thermometer Input Unit
(Economical type)
Isolated-type
Two-wire Transmission
Device Input Unit
Isolated-type Analog
Input Unit
Isolated-type Pulse
Input Unit
Isolated-type Control
Output Unit
Isolated-type Power
Voltage Output Unit
Power Transducer Input
Unit
Analog Input Unit
Specifications
Model
CS1W-PTS11
CS1W-PTS12
CS1W-PTS51
CS1W-PTS55
CS1W-PTS52
CS1W-PTS56
CS1W-PTW01
CS1W-PDC11
CS1W-PDC55
CS1W-PPS01
CS1W-PMV01
CS1W-PMV02
CS1W-PTR01
CS1W-PTR02
I/O
capacity
4 inputs
4 inputs
4 inputs
8 inputs
4 inputs
8 inputs
4 inputs
4 inputs
8 inputs
4 inputs
4 outputs
4 outputs
8 inputs
8 inputs
Field I/O
isolation
All inputs
isolated.
All inputs
isolated.
All inputs are
isolated
Alle inputs are
isolated
All inputs
isolated.
All inputs
isolated.
All inputs
isolated
All inputs
isolated.
All outputs
isolated.
All outputs
isolated
No isolation
between
inputs.
No isolation
between
inputs.
I/O range/type
B, E, J, K, L, N, R, S, T, U,
WRe5-26,PL II, 100 mV
Pt100 (JIS, IEC), JPt100 ,
Pt50 , Ni508.4
B, J, K, R, S, T, L
Pt100 (JIS, IEC), JPt100
4 to 20 mA, 1 to 5 V
4 to 20 mA, 0 to 20 mA, 0 to
10 V, 10 V, 0 to 5 V, 5 V,
1 to 5 V, 0 to 1.25 V, 1.25 V
4 to 20 mA, 0 to 10 V,
0 to 5 V, 1 to 5 V
Max. counting speed: 20 K
pulses/s (voltage input or no-
voltage semi-conductor in-
put) or
20 pulses/s
(contact input)
4 to 20 mA, 1 to 5 V
0 to 10 V, 10 V,
0 to 5 V, 5 V, 0 to 1 V, 1 V
1 mA, 0 to 1 mA
100 mV, 0 to 100 mV
Accuracy/effective resolution
Standard accuracy: 0.05% of full
scale
Temp coefficient: 0.01%/ C
Effective resolution: 1/64,000
Conversion cycle: 20 ms/4 pts
10 ms/2 pts
Standard accuracy: Larger of
Temp coefficient: 0.01%/ C
Effective resolution: 1/64,000
Conversion cycle:20 ms/4 pts
10 ms/2 pts
Overall accuracy: 0.3% of PV
or 1°C, whichever is larger,
Conversion cycle: 250 ms/4 pts
Overall accuracy: 0.3% of PV
or 0.8°C, whichever is larger,
Conversion cycle: 250 ms/4 pts
Standard accuracy: 0.2%
Temp coefficient: 0.015%/ C
Resolution: 1/4,096
Conversion cycle: 100 ms/4 pts
Standard accuracy: 0.05% of full
scale
Temp coefficient: 0.01%/ C
Effective resolution: 1/64,000
Conversion cycle:20 ms/4 pts
10 ms/2 pts
Standard accuracy: 0.3% full scale.
Resolution 1/16000.
Conversion cycle 250 ms/8 pts
---
Standard accuracy:
Temp coefficient: 0.015%/ C
4,000 (outputs)
Conversion cycle: 100 ms/4 pts
Standard accuracy: 0.1%
Temp coefficient: 0.015%/ C
Resolution (at full scale):
0 to 10 V, 0 to 1 V, or 5 V:
1/8,000
0 to 5 V: 1/4,000
Conversion cycle: 40 ms/4 pts
Standard accuracy: 0.2%
Temp coefficient: 0.015%/ C
Resolution: 1/4,096
Conversion cycle: 200 ms/8 pts
Standard accuracy: 0.2%
Temp coefficient: 0.015%/ C
Resolution: 1/4,096
Conversion cycle: 200 ms/8 pts
0.05% of full scale or 0.1 C
10 V or 1 V: 1/16,000
4 to 20 mA: 0.1%
1 to 5 V: 0.2%
1 digit max.
1digit max.
Main features
Output scaling, measured
value alarms (HH, H, L,
LL), rate-of-change opera-
tion and alarms, input dis-
connection alarms, top
hold, bottom hold, valley
hold, zero span adjust-
ment over user-set range
Output scaling, measured
value alarms (HH, H, L,
LL), rate-of-change opera-
tion and alarms, input dis-
connection alarms, top
hold, bottom hold, valley
hold, zero span adjust-
ment over user-set range
Process value alarms
(H, L)
Process value alarm
DO output
Input disconnection
detection
Process value alarms
(H, L)
Process valu alarm
DO output
Input disconnection
detection
Built-in power supply for 2-
wire transmission device
output scaling ( 32,000),
measured value alarms
(HH, H, L, LL), rate-of-
change operation and
alarms, input disconnec-
tion alarms
Output scaling, measured
value alarms (HH, H, L,
LL), rate-of-change opera-
tion and alarms, input dis-
connection alarms, top
hold, bottom hold, valley
hold, total value measure-
ment
Measured value alarms
(H, L), input detection
Built-in sensor power sup-
ply, contact bounce filter,
unit pulse conversion, ac-
cumulative and instanta-
neous value output, 4
instantaneous value
alarms.
Output disconnection
alarms, control output an-
swerback input, output
rate-of-change limit, out-
put high/low limits
Output rate-of-change
limit, Output high/low limit,
Output scaling ( 32,000)
Motor overdrive preven-
tion at startup, output scal-
ing ( 32,000), measured
value alarms (H, L)
Output scaling ( 32,000),
measured value alarms
(H, L)
335