CS1W-CN224 Omron, CS1W-CN224 Datasheet - Page 13

no-image

CS1W-CN224

Manufacturer Part Number
CS1W-CN224
Description
"CABLE,CS1/C200H PRO27,2m"
Manufacturer
Omron
Datasheets

Specifications of CS1W-CN224

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Construction of systems in multivendor environments simplified with protocol macros.
5
The evolution of the
SYSMAC CS1 is
accelerating advances
in the production site.
More Ports for Even More
Serial Device Connections
Truly Seamless Incorporation of OMRON Components
and Other Devices into Networks
When the CPU Unit (Ver. 3.0 or later) or
Serial Communications Board or Serial
Communications Unit (Ver. 1.2 or later)
receive a FINS command containing a
CompoWay/F command (see note 1) via
network or serial communications, the
command is automatically converted to a
protocol suitable for the message and
forwarded using serial communications.
Protocol macros make it easy to create
serial communications protocols
(communications frames, error checks,
retries, error processing, etc.) to match
those of remote communications devices.
Multiple ports are provided for this function.
Each PLC supports up to 16 Serial
Communications Units (32 ports total) and
one Serial Communications Board (with 2
ports). This makes it possible to connect
up to 34 devices with serial
communications at a speed of 38.4 Kbps.
Message length has been increased from
256 to 1,000 bytes to give
communications more power than ever
before.
CompoWay/F (See note 2.)
Host Link FINS
(Possible only with Serial Communications Boards or Serial
Communications Units Ver. 1.2 or later)
When CompoWay/F commands are
enclosed in FINS commands and sent to
Serial Communications Boards or Serial
Communications Units (Ver. 1.2) or
serial ports on CPU Unit Ver. 3.0, the
enclosed CompoWay/F command is
retrieved using a Serial Gateway
Function and sent as a CompoWay/F
command.
Serial Gateway System (Reference)
Serial Gateway
(CPU Unit Ver. 3.0 or later)
(Serial Communications Units/Boards with Ver. 1.2 or later)
Windows-based Software
Simplifies Serial Device
Connections
Note 1: FINS
Abbreviation for Factory Interface Network Service. A
command system for message services common to
OMRON networks. FINS commands can be sent across up
to 8 network levels, including serial communications paths
using a serial gateway. (Possible only with CS/CJ-series
CPU Unit Ver. 2.0 or later.)
Note 2: CompoWay/F
CompoWay/F is an integrated communications protocol
used for OMRON general-purpose serial communications.
It is used by Temperature Controllers, Digital Panel Meters,
Timer/Counters, Smart Sensors, Cam Positioners, Safety
Controllers, etc. (as of July 2004).
Protocol macros for Serial
Communications Units and Boards can be
created using the CX-Protocol, thus
enabling message tracing and greatly
reducing the time involved in connecting
various serial devices.
Component/PLC
OMRON Components
Temperature
Controller
Gateway
Serial
communications
Smart Sensor
FINS command received
Serial Gateway: FINS
command "capsule"
opened and contents
retrieved.
Sent as a CompoWay/F
command
FINS network
259

Related parts for CS1W-CN224