Wiring and Connections
4-7
4-7-1
AC Power Supply Unit
Wiring
Crimp Connectors
Wiring and Connections
Power Supply Unit Wiring
!WARNING
!WARNING
!Caution Disconnect the LG terminal of the Power Supply Unit when performing dielec-
!Caution Use crimp connectors for wiring. Do not connect bare stranded wires directly
!Caution Do not remove the seal from the top of the Power Supply Unit until wiring has
!Caution Tighten the AC power terminal screws to a torque of 0.8 N • m. Loose terminal
!Caution Be sure that the AC power supply voltage remains within the allowable voltage
This section provides basic information on wiring the Power Supply Unit and I/
O Units, and on connecting Programming Devices.
Do not attempt to take any Unit apart while the power is being supplied. Doing
so may result in electric shock.
tric strength tests.
to terminals.
been completed. Remove the seal before operating the Unit to prevent over-
heating.
The following diagram shows the proper connections to an AC power supply.
The AC voltage should be between 100 and 240 V AC (50 to 60 Hz). Refer to
3-2-2 Selecting a Power Supply Unit for details on Power Supply Unit capacity.
Do not touch any of the terminals while the power is being supplied. Doing so
may result in electric shock.
screws can cause fires or errors in operation.
range. For details refer to 2-1-1 Power Supply Units .
The CQM1-PA216 Power Supply Unit is switchable with an input voltage
range of 80 to 138 V AC or 160 to 264 V AC. Refer to 3-2-2 Selecting a Power
Supply Unit for details.
Use round M3.5 crimp connectors of the dimensions shown below for wiring
AC Power Supply Units.
The cross-sectional area of each wire must be 2 mm
Twist the wires.
Insulating transformer
Breaker
An insulating transformer greatly
reduces the noise that may be
induced between the power line and
ground. Do not ground the secondary
side of the insulating transformer.
AC power supply
2
min.
Section 4-7