CS1W-CN313 Omron, CS1W-CN313 Datasheet - Page 42

no-image

CS1W-CN313

Manufacturer Part Number
CS1W-CN313
Description
"CABLE CS1 EXP I/O,30cm"
Manufacturer
Omron
Datasheet

Specifications of CS1W-CN313

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
1-3
1-3-1
20
Expanded System Configuration
Programming
Console bus
Peripheral bus
Host Link
No-protocol
Host Link
No-protocol
1:1 Data Link
NT Link (1:1
mode/1:N mode)
Personal computer
Expanded System Configuration
Serial Communications System
or
Note
Programming Console
RS-232C port
(CPU Unit)
Refer to the CQM1H Programming Manual for the number of words allocated
to each Unit and other information on memory allocation to Units.
1. It is possible to exceed the maximum number of Units without exceeding
2. It is also possible to exceed the maximum number of I/O points (and words
The CQM1H system configuration can be expanded by using the following
serial communications ports.
• CPU Unit built-in ports, 2 ports: Peripheral port and RS-232C port
• Serial Communications Board ports, 2 ports: RS-232C port and RS-422/
the maximum number of I/O points (and words allocated). For example,
with the CQM1H-CPU61, if 12 Units that are allocated 1 word each are
connected, the total number of words allocated will be 13 (including the 1
word allocated for the CPU Unit built-in inputs), which is less than the spec-
ified maximum. The number of Units, however, exceeds the maximum of
11.
allocated) without exceeding the maximum number of Units. For example,
with the CQM1H-CPU61, if 8 Units that are allocated 4 words each are
connected, the maximum number of Units is not exceeded. However, the
total word allocation will be (4
allocated for the CPU Unit built-in inputs), and so consequently the maxi-
mum number of 32 words is exceeded.
485 port (CQM1H-CPU51/61 only)
RS-422A/485 port
(Serial Commu-
nications Board)
Protocol Macro
Host Link
No-protocol
1:1 Data Link
NT Link (1:1
mode/1:N mode)
Peripheral port (CPU Unit)
RS-232C port (Serial Communications Board)
8) + 1 = 33 words (including the 1 word
Protocol Macro
Host Link
No-protocol
1:1 Data Link
NT Link (1:1 mode/1:N mode)
Section 1-3