126
I/O Unit Wiring Precautions
The following diagram shows two methods that can be used to reduce the
large inrush current caused by certain loads, such as incandescent light
bulbs.
Be careful not to damage the output transistor.
Whenever possible, place I/O signal lines and power lines in separate ducts or
raceways both inside and outside of the control panel.
If the I/O wiring and power wiring must be routed in the same duct, use
shielded cable and connect the shield to the GR terminal to reduce noise.
When an inductive load is connected to an I/O Unit, connect a surge suppres-
sor or diode in parallel with the load as shown below.
COM
OUT
Generating a dark current (about 1/3 of the
rated current) through the incandescent bulb.
Suspended duct
R
Example 1
Relay output or
triac output
Relay output or
transistor output
L
In-floor duct
OUT
COM
OUT
COM
Diode
Surge suppressor
COM
COM
OUT
IN
Diode
L
L
DC input
Inserting a regulating resistance.
Example 2
R
+
1 = I/O cables
2 = Power cables
Section 4-8
Conduits