CS1W-CN313 Omron, CS1W-CN313 Datasheet - Page 140

no-image

CS1W-CN313

Manufacturer Part Number
CS1W-CN313
Description
"CABLE CS1 EXP I/O,30cm"
Manufacturer
Omron
Datasheet

Specifications of CS1W-CN313

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Wiring Precautions for
Ground Wires
4-7-2
Expansion I/O Cable
118
Wiring and Connections
Connecting the CPU Block and Expansion I/O Block
!Caution Do not share grounds with other equipment or attaching to the beam of a
Note Definition of EMC:
Note A cable longer than 0.7 m cannot be used.
Wire the grounding wires according to the diagram below.
In order to improve the electromagnetic compatibility (EMC), connect the LG
(
necting cable provided.
The EMC refers to the capacity of equipment represented in terms of emis-
sion, which indicates the degree to which electromagnetic waves produced by
equipment do not affect other communications equipment, and also in terms
of immunity, which indicates the degree of resistance against electromagnetic
disturbance.
building. Improper grounding will cause adverse results.
A CS1-series Expansion I/O Cable must be used. One of these cables is
shown below.
Expansion I/O Cable
Correct
or
DIN-track cable
(Supplied with
the CQM1H PC)
CQM1H
Name
) terminal to the screw on the end plate using the DIN-track con-
Other
equipment
CS1W-CN313
CS1W-CN713
Model
Grounding wire
(Use a wire of at least 2 mm
to ground at a resistance of
less than 100 .)
Short-circuit bar
(Supplied with the CQM1H PC)
Incorrect
CQM1H
Length: 0.3 m
Length: 0.7 m
Specifications
2
Section 4-7
Other
equipment

Related parts for CS1W-CN313