82.031.0101.0 WIELAND ELECTRIC, 82.031.0101.0 Datasheet - Page 508

no-image

82.031.0101.0

Manufacturer Part Number
82.031.0101.0
Description
COUPLING MODULE
Manufacturer
WIELAND ELECTRIC
Datasheet

Specifications of 82.031.0101.0

Connector Type
Modular
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
UET
Analog measurement technology
Isolating set point amplifier
with 2 contact outputs
Important note for user:
The relay outputs must be supplied from the same phase
(e.g. L1).
Caution:
Can only be mounted vertically due to the internal
relays
Dimensions (mm) W x H x D
22,5 x 60,6 x 90,5
506
UET
Description
with measuring points
with LCD display
Versions with other input data available on request
Wiring diagram
Technical data
Operating voltage
Power consumption at 24 V, 2 active relays
Potential free input
Measured input
Input resistance
Maximum permitted input signal
Input protection (interference suppression)
Measuring points for external multimeter
Digital display, LCD 3
Character height
Accuracy of display
Display of range
Resolution
Setpoint adjustment range
Switch outputs
Switching voltage
Maximum switching current
Switching hysteresis
Reproducibility of switching points
Reaction time
Contact
Contact material
Isolation
Isolation against mounting rail
Temperature range
Operating temperature range, series connected at
Storage temperature
Vertical installation without spacing
Vertical installation with spacing of
on measured input potential (for UET)
at 20 °C
at 0...60 °C
Pickup delay
Dropout delay
input and supply
contact and input
contact and supply
open contact
1
/
2
digit
20 mm
Isolating set point amplifier with LCD display or measuring points
Approvals:
Type
UET ±10 V*
UET/LCD ±10 V*
* contains standard signal 0...10 V
See page 513
UET ±10 V
24 V DC ±20%,
ca. 40 mA + output currents
±19.99 V
1 MΩ
±50 V
LC-filter
LC
±1.99 V (acc. ±19,9
with sign and dimension
5 mm
5 mm
±2 digit
±5 digit
±19.99 V
10 mV
±19.99 V
24 V DC
2 A
ca. ±20 mV
ca. ±10 mV
7 ms
5 ms
2 x 1
2 x 1 make contact (SPST, N. O.)
AgCdO + 1 µ Au
500 V DC
500 V DC
750 V
2 kV
0 ...50 °C
0...60 °C
–40...+85 °C
eff.
eff.
L
, CSA
polarised
Display selector
switch
Part no.
57.802.1053.0
57.802.2053.0
±1.99
measured signal)
Std. pack
1
1
Setpoint potentiometer Hi ( )
Setpoint potentiometer Low ( )
Switch output Hi ( ) 2
Switch output Low ( ) 3
Type
UET 20 mA**
UET/LCD 20 mA** 57.802.2253.0
** contains standard signal 4...20 mA
See page 513
UET 20 mA
24 V DC ±20%,
ca. 40 mA +
±19.99 mA
100 Ω
±50 mA (±5 V)
LC-filter
±1.99 V
±1.99 V (acc. ±19.9 V Measured signal)
with sign and dimension
5 mm
±2 digit
±5 digit
±19.99 mA
10 µA
±19.99 mA
24 V DC
2 A
ca. ±20 µA
ca. ±10 µA
7 ms
5 ms
2 x 1
2 x 1 make contact (SPST, N. O.)
AgCdO + 1 µ Au
500 V DC
500 V DC
750 V
2 kV
0 ...50 °C
0...60 °C
–40...+85 °C
For UL: Input to be supplied from Listed
eff.
eff.
output currents
Class II Power Supply
polarised
Part no.
57.806.1253.0
Subject to change without further notice
Std. pack
1
1

Related parts for 82.031.0101.0