MSO-0008P-012 NCC, MSO-0008P-012 Datasheet - Page 105

no-image

MSO-0008P-012

Manufacturer Part Number
MSO-0008P-012
Description
Socket, Relay; 8 Pin Octal
Manufacturer
NCC
Type
Octalr
Datasheet

Specifications of MSO-0008P-012

Number Of Contacts
8
Time Range
0.05 Sec. to 999 Min.
Output Rating
10 A @ 240 VAC Max.; 100 mA @ 5 VDC Min.
Operating Temperature
–23°C to +55°C
AMETEK National Controls Corp. • 1725 Western Drive • West Chicago, Illinois 60185 • Tel: 800-323-2593 • 630-231-5900 • FAX: 630-231-1377 • www.nationalcontrols.com
ORDERING INFORMATION
Single-Phase Undervoltage Monitors
Models 120AZ and 240AZ
FEATURES
LOGIC FUNCTION DIAGRAM
Undervoltage
Setpoint Range
The 120AZ and 240AZ voltage sensors
are intended for use as protection devices
for electronic equipment in the event of a
brown out condition.
Operating Logic: When the input voltage to
the module is greater than the Reset Point
voltage, the relay will be energized and the
LED will be illuminated indicating a normal
line voltage condition. If, however, the input
voltage drops below the Setpoint Voltage
selected by the potentiometer, the relay will
de-energize and the LED will turn off. The
module will remain in this state as long as
the input is less than Reset Point voltage.
Maximum Input Voltage
100% functionally tested
Form C relay output
On-board Trimpot for setpoint adjust-
ment
Circuitry completely encapsulated
Low cost protection against brownouts
Compact size
Superior transient protection
Flame-retardant and solvent-resistant
polyester thermoplastic housing
INPUT VOLTAGE RANGE
Output Relay
and LED
0 to 132 VAC 50/60 Hz
0 to 264 VAC 50/60 Hz
Reset Point
0 Volts
Set
Point
File #E65038
On
Off
UNDERVOLTAGE SETPOINT RANGE
156 to 199 VAC
78 to 99 VAC
SPECIFICATIONS
INPUT
Operating Voltage Ranges:
Model 120AZ: 0 to 132 VAC 50/60 Hz
Model 240AZ: 0 to 264 VAC 50/60 Hz
Max. Power Consumtion:
Model 120AZ: 2.6VA at 132 VAC
Model 240AZ: 4.5VA at 264 VAC
CONTROL
Adjustment: On-board Trimpot
Undervoltage Setpoint Range:
Model 120AZ: 78 to 99 VAC
Model 240AZ: 156 to 99 VAC
Reset Point Voltage:
Model 120AZ: 104 VAC
Model 240AZ: 209 VAC
Repeatability: ±0.5% for fixed conditions; ±1%
over temperature range
Voltage Sense Accuracy: ±2% at 25°C
Power Off Reset Time: 150 ms max.
OUTPUT
Type: Relay contacts, SPDT (1 form C)
Rating: 8 A max. resistive at 250 VAC and
30 VDC; 100 mA at 5 VDC minimum load current
Indication: Green LED; ON for normal condition
PROTECTION
Transient Voltage: 30 joule metal oxide varistor
Dielectric breakdown: 3000 Vrms terminal to
mounting1500 Vrms input to output
Insulation resistance: 100 megohms min.
between terminals and case
MECHANICAL
Termination: .25” x.032” male fast-on terminals
Mounting: Surface mount with one #8 screw
Life:
Mechanical: 10,000,000 cycles min.
Electrical: 100,000 cycles min.
ENVIRONMENTAL
Storage temperature: -40°C to 85°C
Operating temperature: -23°C to 55°C
Humidity: 95% relative max.
RESET POINT VOLTAGE
104 VAC
209 VAC
PART NUMBER
VNC-120AZ-341
VNC-240AZ-345
VOLTAGE MONITORS
CLEARANCE HOLE
FOR #8 SCREW
ADJ USTMENT ACCESS
85
90
UNDERVOLTAGE SETPOINT
78
UNDERVOLTAG E
National Controls
Corporation
West Chicago, IL.
60185
UNDERVOLTAGE DETECTO
Model No: VNC-120AZ-341
Range: 78-132 VAC, 2.6 VA
Contacts:
8 AMP, 1/3 HP, 120/240 VAC
50/60 HZ
SETPOIN T
95
.250 X .032 MALE
SPADE TERMINAL
99
Voltage
R
Normal
(5 PL. )
(31.75 mm)
NORMAL VOLTAGE
INDICATOR (GREEN LED)
1.25 MAX
5659/12/94
C
R
R
.885
E65489
N.C.
VOLTAGE
Input
COM .
INPUT
5-5
N.O.