MSO-0008P-012 NCC, MSO-0008P-012 Datasheet - Page 60

no-image

MSO-0008P-012

Manufacturer Part Number
MSO-0008P-012
Description
Socket, Relay; 8 Pin Octal
Manufacturer
NCC
Type
Octalr
Datasheet

Specifications of MSO-0008P-012

Number Of Contacts
8
Time Range
0.05 Sec. to 999 Min.
Output Rating
10 A @ 240 VAC Max.; 100 mA @ 5 VDC Min.
Operating Temperature
–23°C to +55°C
AMETEK National Controls Corp. • 1725 Western Drive • West Chicago, Illinois 60185 • Tel: 800-323-2593 • 630-231-5900 • FAX: 630-231-1377 • www.nationalcontrols.com
3-2
Digital Temperature Controller
TC140 Series
FEATURES
The Model TC140 is a Digital Temperature
Controller which features an independent
count-up timer. The controller uses a Type
K thermocouple and is microprocessor con-
trolled. The regulation temperature can be
set in one degree increments within speci-
fied limits. Hysteresis, Offset and Fahrenheit
or Celsius are selected via front panel
switches. The HEAT ON light indicates out-
put relay activation. Actual sensed tempera-
ture is normally shown on the digital display.
The control has diagnostic messages for
open probe and memory failure.
Operating Logic: The timer function is
started by pressing the TIME START but-
ton. The digital display will then alternate
between probe temperature and elapsed
time in hours and minutes. The timer func-
tion is cancelled by pressing the TIME
START button again.
Setting Regulation Point: Press the TEMP
button momentarily. The display will flash
SET and PNT briefly then flash the setpoint
value. The
used to adjust the temperature regulating
setpoint. Press the TEMP button again to
cause the control to regulate to the new set-
point.
Setting Hysteresis: The turn-on and turn-
off temperature around a setpoint can be
Compact design
Easy-to-read 4-digit LED display
Time displays in hr./min.
Temperature display in Fahrenheit or
Celsius
Non-volatile storage of programmed
parameters
Watchdog timer ensures reliability
4-button, moisture-resistant keyboard
using snap-action sealed switches
Diagnostic messages for fault condi-
tions
Front panel keyboard programming of
time and temperature
HEAT ON indicator
Accurate and durable thermocouple
temperature sensing
Convenient operating voltage ranges
Heavy duty stainless steel front panel
TEMPERATURE MONITORS/CONTROLS
File #E104595
and
buttons can now be
ORDERING INFORMATION
*All transformer wires are 8” long: 120V Primary Black/White; 220V Primary Black/Black
separately adjusted to ±20°F. Press and
hold the
ond. The display will alternate between ON
and the turn-on value. The
tons can now be used to change this value.
Press the TEMP button again and the OFF
value will be displayed. The
tons can now be used to change the OFF
value. Pressing the TEMP button again will
return the control to normal operation and
will store the new settings. The hysteresis
is set to -1°F, +0°F as shipped from the
factory.
Setting Offset: The displayed value can be
changed by ±20°F relative to actual sensed
temperature value. This feature corrects for
disparity of location of the probe and the
volumetric center of the heating chamber.
Press and hold the TIME and TEMP but-
tons, then also press and hold the
will flash OFF and SET briefly then will flash
the offset value. At this point, the
buttons can be used to adjust the offset.
Pressing the TEMP button programs the
control for the new value. The offset is set
to 0 as shipped from the factory.
Type K Thermocouple, Bead Tip Probe, 6’
Type K Thermocouple, Perforated Probe, 24”
Type K Thermocouple, Probe with 6’ Lead
Type Ke Thermocouple, Probe with 10’ Lead
Type K Thermocouple, Perforated Probe, 48”
Type K Thermocouple, Perforated Probe, 72”
Type K Thermocouple, Probe with Flange
Type K Thermocouple, Ring Lug Mount
buttons. After one second the display
,
and TEMP buttons for .5 sec-
INPUT VOLTAGE
198 to 242 VAC
90 to 135 VAC
18 to 28 VAC
ACCESSORY
and
and
and
but-
and
but-
Diagnostic Messages: An open
probe will cause the digital dis-
play to show PROB and will dis-
able the output until input voltage
is removed and re-applied. If a
memory loss or failure occurs, the
digital display will show FAIL and
the output will be disabled. Input
voltage should be removed and
re-applied. If the FAIL message is
gone, recheck programmed param-
eters and resume operation. If the
FAIL message reappears, contact
the factory for service.