Programming Examples
Using C1000H
Functions and User Programs
7-3-3 Ladder Programming Example
124
10 V
Output
condition
0 V
Output
Output: 0 to 10 V
0000
25503 (ER)
06400
25507 (<)
25507 (<)
Relationship Between Input Data and Output Signals
Example programs are shown below for the C500-DA101 Analog Output Unit
mounted in the C1000H.
The conversion data is stored in DM 0100. The Unit uses IR 010 through IR 013.
Only the programming for point 1 (IR 010) is shown.
Program for BCD Data:
0FFF
(4095)
Digital
value
5 V
(20 mA)
1 V
(4 mA)
Output
CMP(20)
BIN(23)
Output: 1 to 5 V, 4 to 20 mA
0000
DM 0100
DM 0100
#4096
06400
010
Compares the content of
DM 0100 with 4096.
If the data is less than
4096, the data is con-
verted to binary and
transferred to the Unit.
If the data is not con-
vertible, IR 06400 is
turned ON.
0FFF
(4095)
Digital
value
Section 7-3

Related parts for C500DA101