C500DA101 Omron, C500DA101 Datasheet - Page 191

no-image

C500DA101

Manufacturer Part Number
C500DA101
Description
ANALOG OUTPUT UNIT
Manufacturer
Omron
Datasheet

Specifications of C500DA101

Leaded Process Compatible
No
Peak Reflow Compatible (260 C)
No
No. Of Analog Outputs
4
Lead Free Status / RoHS Status
Contains lead / RoHS non-compliant
Upper/Lower Limit
Enable Bits
Upper/Lower Limit
Enabled Flags
180
Functions
To enable the upper/lower limit function, turn ON the Upper/Lower Limit Enable
Bit for each output point. These bits are read/write.
To check whether the upper/lower limit function is active, monitor the status of
the Upper/Lower Limit Enabled Flag for each output point. These flags are read-
only.
Example: Output of 4 to 20 mA for 0 to 300_C
When the lower and upper limits are set to 45_C and 270_C, respectively, output
signals will be restricted to 6.4 mA at 45_C or lower and to 18.4 mA at 270_C or
higher.
Output Point 1
14
14
41
42
Address
0
8
1 to 15 Lower Limit
1 to 15 Upper Limit
Output
signal
Bit
Upper/Lower Limit Enable Bit
BCD/Binary Mode Bit
Function
Lower limit
45_C
Conversion data
Upper limit
270_C
ON
(Enabled)
ON (BCD)
0045
0270
BCD mode
Hex
Hex
Section
Settings
ON
(Enabled)
OFF
(Binary)
002D
010E
Binary
mode
Hex
Hex
9-4