C500DA101 Omron, C500DA101 Datasheet - Page 159

no-image

C500DA101

Manufacturer Part Number
C500DA101
Description
ANALOG OUTPUT UNIT
Manufacturer
Omron
Datasheet

Specifications of C500DA101

Leaded Process Compatible
No
Peak Reflow Compatible (260 C)
No
No. Of Analog Outputs
4
Lead Free Status / RoHS Status
Contains lead / RoHS non-compliant
DIP Switches for Setting
Voltage Output Ranges
148
Settings and Wiring
Output
1
Output
2
Output
3
Output
4
Output
5
Output
6
Output
7
Output
8
Note
DIP switch pin
DIP switch pin
When a voltage output is set, it is also necessary to set the voltage output range
DIP switch pins under the terminal block on the back of the Unit to the same volt-
age output range.
As shown in the following diagram, the DIP switches correspond in order from
top to bottom to outputs 1 to 8. In the factory settings, all outputs are set to the 0 to
10 V range.
4
3
2
1
1. Outputs will not be correct if more than one DIP switch pin is turned ON. Turn
2. When the output signal range is set to 4 to 20 mA or to 0 to 20 mA, the out-
3. Voltage output range DIP switch settings are enabled when the power sup-
ON only one of the pins shown above.
puts will not be affected by the settings of these DIP switch pins.
ply to the PC is turned ON.
No.
–10 to 10 V
–5 to 5 V
0 to 10 V
0 to 5 V
Voltage mode
Voltage mode
When mounting the terminal block, insert the connector correctly
into the circuit board and then push the terminal block all the way in.
Enabled
Enabled
Enabled
Enabled
ON
ON
Disabled
Disabled
Disabled
Disabled
OFF
OFF
Section
OFF
OFF
ON
OFF
Factory
Factory
setting
9-2