9-1-3 Description of Parts
9-1-4 Indicators
142
Specifications and General Information
Front
Model label
Indicator
cover
Set screw
Terminal
block
Set screw
RUN
ERROR
RANGE
Indicator
Front
(With Terminal Block
and Cover Removed)
Green
Red
Red
Color
Output
1
Output
2
Output
3
Output
4
Output
5
Output
6
Output
7
Output
8
Lit while the Unit is operating normally. Turns OFF when an
error occurs. The Unit will stop operating.
This indicator flashes when the total number of write
operations to EEPROM reaches 5,000 or 10,000.
Lights or flashes in the following situations.
With Scaling
Output signal range of 0 to 10 V, 0 to 5 V, 0 to 20 mA, or 4 to
20 mA:
Lights when conversion data is smaller than 0 or greater than
4095, and turns OFF when conversion data is between 0 and
4095.
Output signal range of –5 to 5 V or –10 to 10 V:
Lights when conversion data is smaller than –2048 or greater
than 2047, and turns OFF when conversion data is between
–2048 and 2047.
Without Scaling
Lights when conversion data is smaller than the scaling lower
limit or greater than the scaling upper limit, and turns OFF
when conversion data is between the scaling lower limit and
upper limit.
Internal memory error.
Incorrect data settings.
Disconnected external 24 VDC power supply.
Rear
Function
Backplane
connector
DIP switches for
setting output
ranges
Allocated I/O
two/four-word
mode switch
Switch for setting
operation when PC
power is
interrupted
Section
9-1