C500DA101 Omron, C500DA101 Datasheet - Page 99

no-image

C500DA101

Manufacturer Part Number
C500DA101
Description
ANALOG OUTPUT UNIT
Manufacturer
Omron
Datasheet

Specifications of C500DA101

Leaded Process Compatible
No
Peak Reflow Compatible (260 C)
No
No. Of Analog Outputs
4
Lead Free Status / RoHS Status
Contains lead / RoHS non-compliant
84
Memory Map
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
Read/
write
46
47
48
49
50
51
52
53
map word
Memory
00 to 15
00 to 15
00 to 15
00 to 15
00 to 15
00 to 15
00 to 15
00 to 15
Bits
---
1 to 16
1 to 16
1 to 16
1 to 16
1 to 16
1 to 16
1 to 16
Input
point
Pointer word
Input point enable bits
BCD/binary select bits
Scaling enable bits
Averaging enable bits
Filtering enable bits
Peak hold enable bits
Low alarm enable bits
Function
The pointer word is used to set the
starting location in the Unit memory
map for the I/O READ and I/O
WRITE instructions that are executed
in ladder logic in the CPU Unit. This
allows the user to selectively read
and write parts of the Unit memory
map.
These bits are turned ON by the user
to enable/disable each input point.
The Unit scans only input points that
are enabled. The default value is all
input points enabled.
These bits are turned ON or OFF by
the user to select the data format
used by each input point.
ON:
OFF:
This selection specifies the format of
the conversion data in words 01 to16.
BCD and binary can be used at the
same time for different input points.
NOTE: When specifying a data for-
mat for an input point, all Unit
memory map words for that specific
input point should have the same for-
mat. Mixing formats for an input point
will cause erroneous results to be
reported.
The default value is BCD (ON) for all
input points.
These bits are turned ON by the user
to enable/disable the scaling function
for each input point. The default value
is disabled (OFF) for all input points.
These bits are turned ON by the user
to enable/disable the Averaging
function for each input point. The
default value is disabled (OFF) for all
input points.
These bits are turned ON by the user
to enable/disable the filtering function
for each input point. The default value
is disabled (OFF) for all input points.
These bits are turned ON by the user
to enable/disable the peak hold
function for each input point. The
default value is disabled (OFF) for all
input points.
These bits are turned ON by the user
to enable/disable the low alarm
function for each input point. The
default value is disabled (OFF) for all
input points.
BCD
Binary
Description
Section
5-5