C500DA101 Omron, C500DA101 Datasheet - Page 162

no-image

C500DA101

Manufacturer Part Number
C500DA101
Description
ANALOG OUTPUT UNIT
Manufacturer
Omron
Datasheet

Specifications of C500DA101

Leaded Process Compatible
No
Peak Reflow Compatible (260 C)
No
No. Of Analog Outputs
4
Lead Free Status / RoHS Status
Contains lead / RoHS non-compliant
External Power Supply
9-2-4 Wiring
Settings and Wiring
Current output
4 to 20 mA
or
0 to 20 mA
Note The external power supply to be used must meet the following specifications.
:
The terminal arrangement is as shown in the following diagram.
This Analog Output Unit must receive an external power supply of 24 VDC ±5%.
The current consumption is 0.8 A.
When using the external power supply, adjust the output voltage between A0 and A1 or
between B0 and B1 to 24 ±0.3 V.
External 24 V +
External 0 V
None
Output 1 +
Output 1 –
Output 2 +
Output 2 –
Output 3 +
Output 3 –
Output 4 +
Output 4 –
Output 5 +
Output 5 –
Output 6 +
Output 6 –
Output 7 +
Output 7 –
Output 8 +
Output 8 –
24 VDC
Output voltage: 24 V
Voltage adjustment range: ±5% min.
Constant-voltage output accuracy: ±3% max.
Output ripple: 400 mV
Current capacity: 1 A min. per Unit
p-p
External 24 V +
External 0 V
None
Output 1 +
Output 1 –
Output 2 +
Output 2 –
Output 3 +
Output 3 –
Output 4 +
Output 4 –
Output 5 +
Output 5 –
Output 6 +
Output 6 –
Output 7 +
Output 7 –
Output 8 +
Output 8 –
max.
or
Voltage output
0 to 10 V
0 to 5 V
–5 to 5 V
or
–10 to 10 V
:
Section
24 VDC
151
9-2

Related parts for C500DA101