C500DA101 Omron, C500DA101 Datasheet - Page 147

no-image

C500DA101

Manufacturer Part Number
C500DA101
Description
ANALOG OUTPUT UNIT
Manufacturer
Omron
Datasheet

Specifications of C500DA101

Leaded Process Compatible
No
Peak Reflow Compatible (260 C)
No
No. Of Analog Outputs
4
Lead Free Status / RoHS Status
Contains lead / RoHS non-compliant
9-1
9-1-1 Specifications
General Specifications
Performance Specifications
136
Specifications and General Information
Number of analog
output points
Output signal
range
Max. output current Voltage outputs
External output
impedance
Max. load
resistance
Power supply from
PC
External power
supply
Resolution
Conversion data
ranges
i
Item
Specifications and General Information
8
Voltage outputs
Current outputs
Voltage outputs
Current outputs
Voltage outputs
5 VDC (supplied from Backplane)
24 VDC ±5%
1/4095 (full scale)
Without Scaling
Voltage outputs
Current outputs
Voltage outputs
With Scaling
Range: Scaling lower limit to scaling upper limit (see note below)
The upper and lower limits must be within the following ranges.
BCD mode: Decimal values –7999 to 7999 (F999 to 7999
Binary mode: Decimal values –32767 to 32767 (8001 to 7FFF
Note:
The scaling lower limit can be greater than the scaling upper limit, in which case reverse
scaling will be performed.
All general specifications of the C500-DA501 Analog Output Unit conform to
those of the C Series, except the following:
Ambient operating
temperature
0 to 10 V
0 to 5 V
–5 to 5 V
–10 to 10 V
0 to 20 mA
4 to 20 mA
10 mA
0.5 Ω max.
750 Ω max.
10 kΩ min.
0 to 10 V
0 to 5 V
0 to 20 mA
4 to 20 mA
–5 to 5 V
–10 to 10 V
Item
Settable as shown on the left for each output point.
(All 8 output points are factory-set to 0 to 10 V.)
Voltage outputs: The range is set using the DIP switches
on the rear panel and the voltage output range
short-circuit pins on the front panel
short-circuit pins on the front panel.
Current outputs: The range is set using the DIP switches
on the rear panel.
BCD mode: Unsigned decimal values in BCD, 0 to 4095
(0000 to 4095
Binary mode: Unsigned decimal values in binary 0 to
Binary mode: Unsigned decimal values in binary, 0 to
4095 (0000 to 0FFF
(BCD or binary can be set for each output point.)
BCD mode: Signed decimal values in BCD, –2048 to 2047
(A048 to 2047
Binary mode: Signed decimal values in binary, –2048 to
2047 (F800 to 07FF
(BCD or binary can be set for each output point.)
8 points with voltage outputs: 0 to 55_C
4 points with voltage or current outputs: 0 to 50_C
8 points with current outputs: 0 to 45_C
Specification
Hex
Hex
)
)
Hex
Hex
Hex
)
Hex
Specification
)
)
)
Section
9-1