C500DA101 Omron, C500DA101 Datasheet - Page 187

no-image

C500DA101

Manufacturer Part Number
C500DA101
Description
ANALOG OUTPUT UNIT
Manufacturer
Omron
Datasheet

Specifications of C500DA101

Leaded Process Compatible
No
Peak Reflow Compatible (260 C)
No
No. Of Analog Outputs
4
Lead Free Status / RoHS Status
Contains lead / RoHS non-compliant
Output Signals
Scaling Enable Bits
Scaling Enabled Flags
Examples of Positive Scaling
176
Functions
Example 1: 0 to 5 V output for 0 to 100%
Scaling Lower Limit < Scaling Upper Limit
Scaling
lower limit
Conversion data
Conversion data
When the scaling lower limit is smaller than the scaling upper limit, the lower limit
corresponds to output signal level 0%, the upper limit corresponds to output sig-
nal level 100%, and positive scaling is performed.
When the scaling lower limit is greater than the scaling upper limit, the lower limit
corresponds to output signal level 100%, the upper limit corresponds to output
signal level 0%, and reverse scaling is performed.
Conversion data set in engineering units is converted into a rate of 0% to 100%
(0 to 4095) according to the scaling upper and lower limits, subject to conver-
sion, and then generated as output signals.
To enable scaling, turn ON the Scaling Enable Bit for each output point. These
bits are read/write.
To check whether the scaling function is active, monitor the status of the Scaling
Enabled Flag for each output point. These flags are read-only.
Output Point 1
13
14
17
18
Address
Scaling
upper limit
0
8
1 to 15 Scaling Lower Limit
1 to 15 Scaling Upper Limit
Bit
Scaling Enable Bit
BCD/Binary Mode Bit
Example 2: 4 to 20 mA output for –100 to 200_C
Scaling Lower Limit > Scaling Upper Limit
Scaling
upper limit
Function
Conversion data
Conversion data
Scaling
lower limit
ON
(Enabled)
ON (BCD)
0000
0100
Example 1
Hex
Hex
Section
Settings
ON
(Enabled)
ON (BCD)
8100
0200
Example 2
Hex
Hex
9-4