Output Ramps
9-1-2 Overview
Specifications and General Information
The C500-DA501 is a Special I/O Unit for the C500, C1000H, C2000H, CVM1,
and CV-series PCs. It has eight analog output points and the following functions.
• Output signal range can be selected for each output point (0 to 10 V, 0 to 5 V, –5
• Either BCD or binary format can be selected for the conversion data for each
• Scaling can be set for each output point.
• Upper/lower limits can be set for each output point.
• An output ramp can be set for each output point.
• High-speed conversion can be set for all eight output points (only when scal-
Output ramps can be used to make output signals change at a specified rate to
prevent sudden changes in response to changes in conversion data.
to 5 V, –10 to 10 V, 0 to 20 mA, or 4 to 20 mA).
output point.
ing, upper/lower limits, and output ramps are not used).
Example: 0
Output Signal Range Selection
Scaling
Conversion data can be set in
engineering units. The scaling
upper and lower limits are set.
Note Reverse scaling (lower limit: 100%, upper limit: 0%) is also possible.
Scaling
lower limit
Conversion
Output signal
(V)
Conversion data
Output signal
range can be
set.
Scaling
upper limit
Changes in conversion
data
300
Conversion
Set time
(Resolution)
Either BCD or
binary can be
set.
Set time
BCD/Binary Mode Selection
Upper/Lower Limits
Output signals remain constant when
conversion data exceeds the upper limit
or drops below the lower limit.
Upper
limit
Lower
limit
Set time
Lower
limit
Section
Time
Upper
limit
141