C500DA101

Manufacturer Part Number
C500DA101
Description
ANALOG OUTPUT UNIT
Manufacturer
Omron
Datasheet

Specifications of C500DA101

Leaded Process Compatible
No
Peak Reflow Compatible (260 C)
No
No. Of Analog Outputs
4
Lead Free Status / RoHS Status
Contains lead / RoHS non-compliant
Output Ramp Set Time
Examples of Reverse Scaling
9-4-3 Output Ramps
Functions
Example 3: 0 to 5 V output for 0 to 100%
Conversion data
Note
Output Point 3
The output ramps make output signals gradually change with time to prevent
sudden changes in response to Conversion data fluctuations. The time required
to change the present value to a new value is set in ms. This function can be set
individually for each output point.
When an output signal reaches the new value after the ramp set time elapses,
the output signal holds that value if there is no new change in the conversion
data. Therefore, when using this function, change conversion data only if output
needs to be changed.
To enable the output ramp function, set the output ramp set time, turn ON the
Output Ramp Enable Bit, and turn ON the Parameter Update Bit in the allocated
I/O words. Conversion data in RAM will be rewritten and the Analog Output Unit
will generate output signals according to the new parameter settings.
Set the output ramp set time in ms. The setting range depends on the data for-
mat (BCD or binary mode) as shown in the following table. The output ramp set
time must be 8 ms or greater.
13
14
21
22
Output ramp set time
(Unit: ms)
1. If a value outside the setting range is set, other data will not be written (to
2. Because conversion data is updated every 8 ms, the time required for an
Address
RAM).
output signal to reach a new value is a multiple of 8 ms. Therefore, the maxi-
mum output ramp set time accuracy is + 8 ms.
2
10
1 to 15 Scaling Lower Limit
1 to 15 Scaling Upper Limit
Bit
Scaling Enable Bit
BCD/Binary Mode Bit
0008 to 7999
(Decimal: 8 to 7999)
Example 4: 4 to 20 mA output for 300 to 0_C
Function
BCD
Hex
Conversion data
ON
(Enabled)
ON (BCD)
0100
0000
0008 to 7FFF
(Decimal: 8 to 32767)
Example 3
Hex
Hex
Section
Settings
Binary
Hex
ON
(Enabled)
ON (BCD)
0300
0000
Example 4
Hex
Hex
177
9-4