C500DA101 Omron, C500DA101 Datasheet - Page 90

no-image

C500DA101

Manufacturer Part Number
C500DA101
Description
ANALOG OUTPUT UNIT
Manufacturer
Omron
Datasheet

Specifications of C500DA101

Leaded Process Compatible
No
Peak Reflow Compatible (260 C)
No
No. Of Analog Outputs
4
Lead Free Status / RoHS Status
Contains lead / RoHS non-compliant
Precautions
Differential Source with Multiple Points (Single Reference)
Installation, Settings, and Wiring
Note Only one ground should be connected at the source when multiple points are
connected to the Unit.
Observe the following precautions when wiring the Analog Input Unit.
• Use shielded twisted-pair cables for signals lines.
• Keep all cables as short as possible.
• Analog signal cables contain positive and negative lines. Do not reverse the
• Never wire low-voltage cables (such as analog input cables) near high-voltage
• Use wiring ducts for all cables and place signal cables and power cables in
• Do not bend the cables past their natural bending radius.
• Do not wire cables in places subject to vibration.
• Short the positive and negative terminals on all unused inputs to reduce exter-
polarity when wiring the inputs.
cables.
separate ducts.
nal interference. If the terminals are not shorted, an out-of-range error may oc-
cur, causing the ERROR indicator to light.