4-3 High-speed 1:N NT Link
4-20
Using a Programming Console
If the PT is connected to the Host Link port (RS-232C port), connect the Programming Con-
sole to the CPU Unit and set the following values at the specified addresses of the PLC
Setup.
160
161
166
Reference
Setting the Front Panel Switches
Using RS-232C
Set DIP switch pin 4 or 5 of the CPU Unit according to the port to which the PT is connected,
as follows:
address
Setup
RS-232C port
Mainly connected to
an RS-232C device.
(Can be connected to
a computer running
the CX-Programmer.)
Peripheral port
Mainly connected to a
Programming Device.
PLC
8200 hex
000A hex
000@ hex
If the PT is connected to the peripheral port make the above settings in words 144, 145,
and 150 of the PLC Setup instead of 160, 161, 166.
Setting to write
Specifies using the Host Link port in 1:N NT Link Mode.
Baud rate: High-speed (115,200 bps)
If only one PT is connected to the port and it has a unit
number of 0, replace the box at the left with 1. Otherwise,
replace the box with the highest unit number of all the PTs
that are connected.
DIP switch (inside battery
compartment)
Turn ON pin 4 when connecting the
PT to the peripheral port (to use the
communications settings in the PLC
Setup).
Turn OFF pin 5 when connecting the
PT to the RS-232C port (to use the
communications settings in the PLC
Setup).