XPSAF5130P SQUARE D, XPSAF5130P Datasheet - Page 107

SAFETY RELAY 300V 2.5A PREVENTA

XPSAF5130P

Manufacturer Part Number
XPSAF5130P
Description
SAFETY RELAY 300V 2.5A PREVENTA
Manufacturer
SQUARE D
Datasheet

Specifications of XPSAF5130P

Contact Current Max
30mA
Contact Voltage Dc Nom
24V
Contact Configuration
3NO
Relay Mounting
DIN Rail
External Height
66mm
External Width
114mm
External Depth
22.5mm
Rohs Compliant
Yes
10
10
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
9
9
Presentation
Preventa™ safety controller modules XPSMP are
designed to conform with category 4 of the standard
EN 954-1/ISO 13849-1.
They enable two independent safety functions
(selected from a choice of 15 pre-defined
configurations) to be performed using the same
product. Configuration selection is easily made using
3 buttons on the front cover of the module.
(1) Automatic start: there is no start contact or it is jumpered.
(2) Tool zone guard with 3
Presentation:
page 2/106
2/106
Presentation
Operating principle
Functions disabled
Emergency stop monitoring,
1-channel wiring (category 2)
Emergency stop monitoring,
2-channel wiring, or guard
monitoring (category 4)
Guard monitoring for injection press
or blowing machine (category 4)
Enabling grip switch monitoring
(3 position switch) (category 4)
Sensing mat and edges monitoring
(category 3)
Relay output light curtain
monitoring (category 4)
Non-contact safety interlock switch
monitoring (category 4)
Unmonitored start: the output is activated on closing of the start contact.
Monitored start: the start input is monitored so that there is no start-up in the event of the start contact being jumpered or the start circuit being closed for
more than 10 seconds.
Start-up is triggered following activation of the start button (push-release function) on opening of the contact.
Additional rear guard (optional) with automatic start. The opening of the guard cuts all outputs.
rd
switch.
Characteristics:
page 2/107
Configuration
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
Safety automation system solutions
Preventa™ safety controllers type XPSMP
With pre-defined functions
These 15 pre-programmed safety functions provide a solution for the majority of
safety applications up to level 4 conforming to the standard EN 954-1/ISO 13849-1,
for example: monitoring Emergency stops, limit switches, safety mats and sensing
edges, enabling switches, coded magnetic switches, type 4 relay output light
curtains conforming to EN/IEC 61496-1 (for example, light curtains type XUS L.
Safety controllers XPSMP incorporate 6 safety outputs (3 per function) and 3
solid-state signalling outputs for signalling to the process PLC.
To aid diagnostics, the modules have LEDs on the front cover which provide
information on the monitoring circuit status. They also indicate and assist selection
of the 2 required configurations.
References:
page 2/108
Synchronization
time
Unlimited
Unlimited
1.5 s
1.5 s
Unlimited
Unlimited
1.5 s
0.5 s
1.5 s
1.5 s
Type of start (1)
Automatic or
unmonitored
X
X
X
X
X
X
X
Dimensions:
page 2/109
Monitored
X
X
X
X
X
X
X
X
Start test
X
X
X
X
X
X
X
Wiring Diagrams:
page 2/110 to 2/117
Notes
Factory setting
Uses both safety
outputs (2)
The start button
acts as start-up
preparation
Mats with circuit
making contacts
Magnetic switches
with 2 contacts,
1 N.O. and 1 N.C.

Related parts for XPSAF5130P