XPSAF5130P SQUARE D, XPSAF5130P Datasheet - Page 182

SAFETY RELAY 300V 2.5A PREVENTA

XPSAF5130P

Manufacturer Part Number
XPSAF5130P
Description
SAFETY RELAY 300V 2.5A PREVENTA
Manufacturer
SQUARE D
Datasheet

Specifications of XPSAF5130P

Contact Current Max
30mA
Contact Voltage Dc Nom
24V
Contact Configuration
3NO
Relay Mounting
DIN Rail
External Height
66mm
External Width
114mm
External Depth
22.5mm
Rohs Compliant
Yes
Wiring diagrams
(1) Jumper for automatic start.
(2) Instantaneous opening safety outputs (stop category 0).
(3) Time delay opening safety outputs (stop category 1).
ESC = External start conditions.
Automatic start
Emergency stop
S11-S12
Automatic start
(without ESC) S13-S14
Linked input
S21-S22
Linked input
S31-S32
Time delay interrupt
Y39-Y40
N.O. output
03-04/13-14/23-24
N.O. output
37-38/47-48/57-58
Signalling output
Y74
Signalling output
Y84
Automatic start
There is no start contact or it is jumpered (wiring between terminals S13 - S14).
Note: Automatic start function is not available on the XPSAV with 2 channel wiring on the inputs. Automatic start function is only available on single channel wiring
on the inputs.
Unmonitored start
The output is activated on closing of the start contact (wiring between terminals S13 - S14).
Monitored start
The start input is monitored so that there is no start-up in the event of the start contact being jumpered or the start circuit being closed for more than 10 seconds.
Start-up is triggered following activation of the start button (push-release function) on opening of the contact (wiring between terminals S33 - S34).
Principle:
page 2/178
XPSAV
Module XPSAV associated with an Emergency stop button with 1 N.C. contact, automatic start or unmonitored start
Functional diagrams
Power-up
Start
Emergency stop
not activated
Emergency
stop
Characteristics:
page 2/178
Logic
channel 1
Logic
channel 2
Tv = 0…300 s
stop activated
Emergency
Output 1
Output 1
Output 2
Output 2
Time delay stop
Start
Emergency
activated
Start
stop not
Safety automation system solutions
Preventa™ safety relay modules type XPSAV
For Emergency stop and switch monitoring
References:
page 2/180
Emergency
Time delay
interrupted
activated
stop
Unmonitored start
Emergency stop
S11-S12
Start button
S13-S14
Linked input
S21-S22
Linked input
S31-S32
Time delay interrupt
Y39-Y40
N.O. output
03-04/13-14/23-24
N.O. output
37-38/47-48/57-58
Signalling output
Y74
Signalling output
Y84
Power-up
Wiring Diagrams:
page 2/181
Emergency stop
Start
not activated
To PLC
Tv = 0…300 s
Emergency stop
activated
Dimensions:
page 2/260
Emergency
activated
Start
stop not
Emergency
Time delay
interrupted
activated
stop
2/181
10
10
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
9
9