XPSAF5130P SQUARE D, XPSAF5130P Datasheet - Page 42

SAFETY RELAY 300V 2.5A PREVENTA

XPSAF5130P

Manufacturer Part Number
XPSAF5130P
Description
SAFETY RELAY 300V 2.5A PREVENTA
Manufacturer
SQUARE D
Datasheet

Specifications of XPSAF5130P

Contact Current Max
30mA
Contact Voltage Dc Nom
24V
Contact Configuration
3NO
Relay Mounting
DIN Rail
External Height
66mm
External Width
114mm
External Depth
22.5mm
Rohs Compliant
Yes
Description (continued)
Safety automation system solutions
Preventa™ safety PLCs
Modular, XPSMF60
Rack, power supply and CPU
RUN
ERR
FB1
FB2
RUN
STOP
PROG
FAULT
FORCE
OSL
BL
RJ45
LED details
Central processing unit XPSMFCPU22
LED
Color
Green
Red
Orange
Green
Red
Orange
Orange
Orange
Orange
Orange
Green
Yellow
(continued)
Status
On
Flashing
Off
On
Flashing
Off
On
On
Off
On
Off
On
Flashing
Off
On
Flashing
Off
On
Flashing
Off
Flashing
Flashing
On
Flashing
Off
On
Flashing
Meaning
Program in operation: CPU in STOP or RUN mode.
A new programming system will be downloaded.
The CPU is in “ERROR” state (see ERROR).
Software error or hardware anomaly detected by the CPU.
The monitoring program (Watchdog) has triggered the
STOP state of the process because the programmed cycle
time has been exceeded. The CPU has stopped the
execution of the user application, ended all hardware and
software tests and all outputs have been reset. The
process can only be started again from the PC.
In the event of all the LEDs being on, restarting has
detected a system error, a new operating system (OS)
must be loaded.
No error detected.
Not used.
Communication on Modbus® serial link active.
Normal service mode, loaded program running, the PLC
receives I/O messages, communication and hardware/
software tests carried out.
The CPU is in “ERROR” state (see ERROR).
The CPU is in STOP mode and no program can be
executed.
The outputs are in the waiting state for the correct supply.
The CPU has stopped the execution of the user
application, ended all hardware and software tests and all
outputs have been reset.
The process can only be started again from the terminal.
CPU operating.
A new programming system will be downloaded.
The CPU is being loaded with a new configuration.
CPU changing from INIT state to STOP state.
The FLASH ROM is being loaded with a new operating
system.
No loading of configuration or operating system.
Program error.
The loading of a new operating system was defective and
the operating system is corrupt.
An error has occurred while writing to FLASH ROM
memory (during updating of the operating system).
One or more I/O errors have occurred.
None of the above errors have occurred.
CPU in RUN mode and force is active.
Program in STOP mode, but force is prepared and
activated if the program restarts.
Force not activated.
Operating system and backup loading active.
COM in INIT_Fail state.
Full duplex mode operation.
Signal collision.
Half duplex mode operation, no collision.
Connection established.