DRT2-ID32BV-1 Omron, DRT2-ID32BV-1 Datasheet - Page 314

no-image

DRT2-ID32BV-1

Manufacturer Part Number
DRT2-ID32BV-1
Description
32 In Vert MIL Connector PNP
Manufacturer
Omron
Datasheet

Specifications of DRT2-ID32BV-1

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Analog Output Terminals
Overview of Analog Slaves
Slave
Model
Data allocated in
Master
Input switching (Sets
number of AD con-
version points)
Input range switching Set using rotary switches: Inputs 0 and 2 share
Node address setting Set using DIP switch.
Baud rate setting
Moving average
Off-wire detection
Scaling, offset com-
pensation, peak/bot-
tom hold, top/valley
hold, rate of change
operations, compara-
tor, user adjustment
(maintenance func-
tion), cumulative
counter (mainte-
nance function), last
maintenance date
(maintenance func-
tion)
Slave
Model
Analog points
Output signal range
Conversion time
AD conversion data
Resolution
Unit power supply
Communications power sup-
ply current consumption
Overall accuracy
Data allocated in Master
25°C
−10 to
55°C
DRT1-AD04
Only analog input values for 4 inputs
Supported. (Set using
DIP switch: Select
either 2 or 4 points)
one setting, and Inputs 1 and 3 share another
setting.
Set using DIP switch.
Supported. (Set using
DIP switch.)
Supported.
Not supported.
DRT1-DA02
2 outputs
1 to 5 V, 0 to 10 V, –10 to 10 V, 0 to 20 mA,
4 to 20 mA (0 to 5 V not supported)
4 ms/2 points
0 to 5 V, 1 to 5 V, 0 to 10 V, 0 to 20 mA, 4 to
20 mA: 0000 to 1770 hex
–10 to 10 V: 8BB8 to 0BB8 hex
Note Signed binary
1/6,000 (full scale)
Supplied by local power supply terminal.
30 mA max.
Voltage output:
0 to 55°C:
Voltage output:
±
Only Analog output values for 2 outputs
0.8% FS
DRT1 Series
DRT1 Series
±
±
DRT1-AD04H
Not supported.
Not supported.
0.3% FS; Current output:
0.6% FS; Current output:
DRT2-AD04
Default: Analog input values for 4 points
The Configurator can be used to allocate peak,
bottom, top, and valley values, rate of change,
comparator results, Generic Status Flags, etc.
Supported (Set using
Configurator: Select
from 1 to 4 points)
• Using DIP switch: Inputs 0 and 1 share set-
• Using Configurator: Inputs 0 to 3 set sepa-
Set using the rotary switches or the Configura-
tor.
Automatically detected: Uses baud rate set for
Master Unit.
Supported. (Set using Configurator.)
Supported. (Set using Configurator.)
ting, Inputs 2 and 3 share setting.
rately.
±
0.4% FS
Default: Analog output values for 2 points
DRT2-DA02
0 to 5 V, 1 to 5 V, 0 to 10 V, –10 to 10 V, 0 to
20 mA, 4 to 20 mA
2 ms/2 points
0 to 5 V, 1 to 5 V, 0 to 10 V, 0 to 20 mA, 4 to
20 mA: 0000 to 1770 hex
–10 to 10 V: F448 to 0BB8 hex
Note Two’s complement
Supplied by communications power supply.
120 mA max.
−10 to 55°C:
Voltage output:
±
The Configurator can be used to allocate
Generic Status Flags.
0.8% FS
DRT2 Series
DRT2 Series
±
0.6% FS; Current output:
DRT2-AD04H
Not supported.
Section 7-1
293

Related parts for DRT2-ID32BV-1