Cumulative Counter
Setting Using the DeviceNet Configurator
Temperature Input Terminals
1,2,3...
Note
Note The following table shows the time divisions and number of measurements.
3. Return to the General Tab, click the Download Button, and then click the
4. Click the OK Button and exit the window.
The cumulative counter integrates the temperature input value over time to
determine the amount of heat endured by a sensor or device. calculates a
time integral of analog input values over time. The cumulative value can be
calculated in hours ( ° C × hours or ° F × hours) or minutes ( ° C × minutes or ° F ×
minutes).
For example, when the units are set to hours, a cumulative value of 100 hours
indicates a temperature value equivalent to 100 ° C continuing for one hour.
The value stored in the four-byte area (two words) is the integral value for 300
time divisions. The data is displayed according to the set conditions. (See
notes 1 and 2.)
Monitor values can also be set in the Unit. When the cumulated count value
exceeds the set monitor value, the Cumulative Counter Flag in the area for
Generic Status Flags turns ON.
1. When ° F units are selected, the integration is performed on the ° F values.
2. Even if the 1/100 display mode is selected, the integration is performed on
3. The meaning of the integral value depends on the decimal point position
1. Double-click the icon of the Temperature Input Terminal to be set in the
Temperature
input value
Hours
Minutes
Reset Button to reset the Unit.
the original ( × 100) temperature values.
for the temperature values.
Main Window and open the Edit Device Parameters Window. (From the
Maintenance Mode Window, click the right mouse button over the Slave
icon and select Parameters and Edit.)
Units
Time division
(See note.)
12 seconds
200 ms
Time division
Integral value
( ° C × hours or ° C × minutes)
300
300
Number of measurements
Time
Section 7-6
427