Allocating User-
defined Data
DeviceNet Remote I/O Communications
Note
Default Connection Path (General-purpose Slave)
This method is possible only with a CS/CJ-series DeviceNet Unit and user-
defined allocations.
In the Master’s Edit Device Parameters Window, select the Smart Slave to be
set, and specify the connection in the Advanced Setting Window. Select the
I/O data (pattern) in the connection path setting.
In the Master’s Edit Device Parameters Window, allocate Slave I/O.
1. For details on connections and connection paths, refer to Appendix B De-
2. Master Unit settings take precedence and so it is not necessary to set the
The setting example below is for allocating 16 inputs, 8 outputs, and Generic
Status Flags for a General-purpose Slave. For details on the setting method
for Analog Slaves, refer to 7-4-2 I/O Data Allocation Methods.
Example: Using 16 inputs, 8 outputs, and status information.
Setting 1 (I/O
Data)
(default setting)
Setting 2 (I/O
Data+Status)
Address
CIO 3200
CIO 3300
CIO 3500
Selection
viceNet Connections in the DeviceNet Units Operation Manual (W380).
Slave’s default connection path.
IN data
OUT data
IN data
OUT data
IN/OUT
15
Real input data None
None
Real I/O data +
status informa-
tion
None
Input Unit
16 inputs
Real output
data
Status informa-
tion
Real output
data
Output Unit
:
:
Generic Status Flags
8 outputs
Real input data
Real output
data
Real input data
+ status infor-
mation
Real output
data
Section 3-2
I/O Unit
43