DRT2-ID32BV-1 Omron, DRT2-ID32BV-1 Datasheet - Page 46

no-image

DRT2-ID32BV-1

Manufacturer Part Number
DRT2-ID32BV-1
Description
32 In Vert MIL Connector PNP
Manufacturer
Omron
Datasheet

Specifications of DRT2-ID32BV-1

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
CJ1W-DRM21
Mounting
2-3-2
Settings
Mounting
Mounting Example
Setting and Wiring Hardware
Mounting and Setting Slaves
DRM21
4 HOLD
3
2
1
ESTP
DR1
DR0
ON
The Master Unit is mounted to the Backplane of the PLC in the same way as
other Units are normally mounted. CJ-series Master Units have no Backplane,
so connect the Units together by joining the connectors. For details on mount-
ing Master Units to PLCs, and PLCs to control panels, refer to the applicable
PLC Operation Manual.
The following example shows Slave settings. For details on how to set Slaves,
refer to SECTION 5 General-purpose Slaves to SECTION 7 Analog Slaves.
Remote I/O Terminals are mounted by fixing to a DIN Track, as shown in the
following example.
Secure the bottom of the Slave Unit to a 35-mm DIN Track, or secure the
Slave Unit to the track between two End Plates.
The following diagram shows all Units except the PLC node mounted to DIN
Tracks.
UNIT
NO.
MS
NS
• DRT2-ID16 Remote I/O Terminals (transistor inputs)
• DRT2-OD16 Remote I/O Terminals (transistor outputs)
• DRT2-ID16 Remote I/O Terminals (transistor inputs)
• DRT2-OD16 Remote I/O Terminals (transistor outputs)
Node address: 01
Node address: 02
XWT-ID08 Remote I/O Terminal Expansion Unit
Node address: 03
XWT-OD08 Remote I/O Terminal Expansion Unit
Node address: 04
Master
DIP switches
These pins have the following functions:
Pins 1 and 2: Baud rate
Pins 3: Continue/stop remote I/O communications for error (for Master functions)
Pin 4: Hold/clear I/O for communications error (for Slave functions).
Indicators
Unit No. switch
This rotary switch sets the single-digit hexadecimal
unit number of the Master on the DeviceNet network.
Node address switches
These rotary switches set the double-digit decimal node address of the Unit.
Communications connector
This connector is connected to the Network communications
cable. Communications power is also supplied through this
connector. An XW4B-05C1-H1-D Parallel Connector with
Screws is provided as the node connector.
Remote I/O
Terminal (Input)
Remote I/O
Terminal (Output)
Section 2-3
0
25

Related parts for DRT2-ID32BV-1