DRT2-ID32BV-1 Omron, DRT2-ID32BV-1 Datasheet - Page 446

no-image

DRT2-ID32BV-1

Manufacturer Part Number
DRT2-ID32BV-1
Description
32 In Vert MIL Connector PNP
Manufacturer
Omron
Datasheet

Specifications of DRT2-ID32BV-1

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Off-wire Detection
Last Maintenance
Date
Setting Using the DeviceNet Configurator
Temperature Input Terminals
1,2,3...
■ Setting the Last Maintenance Date of the Unit
4. Return to the General Tab, click the Download Button, and then click the
5. Click the OK Button and exit the window.
6. The comparison results can be checked in the Maintenance Information
When an input sensor is disconnected, the Off-wire Detection Flag turns ON
for each input. The Off-wire Detection Flags are included in the Analog Status
Flags.
When an off-wire condition is detected, the value of AD conversion data is set
to 7FFF hex (7FFF FFFF when 1/100 display mode is being used). When the
input returns to a value within the range that can be converted, the Off-wire
Detection function will automatically be turned OFF, and normal data conver-
sion will resume.
The last maintenance date can be set in the Unit separately for the Unit and
the connected devices. It enables the user to easily determine the next main-
tenance date. The date can be set using the Configurator.
1. Double-click the icon of the Temperature Input Terminal to be set in the
value to a precision of 0.01. For example, when setting 10 ° C, input 1000
for 10.00 ° C.
Reset Button to reset the Unit.
Window or Data comparison between channels Tab.
Main Window and open the Edit Device Parameters Window. (From the
Maintenance Mode Window, click the right mouse button over the Slave
icon and select Parameters and Edit.)
Section 7-6
425