Troubleshooting
462
Errors occurring in
Slaves with outputs
DRT2-OD08(-1)
DRT2-OD16(-1)
DRT2-MD16(-1)
DRT2-ROS16
DRT2-MD16S(-1)
DRT2-OD16TA(-1)
DRT2-MD16TA(-1)
DRT2-OD16ML(X)(-1)
DRT2-OD32ML(-1)
DRT2-MD32ML(-1)
DRT2-OD32B/BV(-1)
DRT2-MD32B/BV(-1)
DRT2-OD16SL/SLH(-1)
DRT2-OD32SL/SLH(-1)
DRT2-MD32SL/SLH(-1)
DRT2-OD04CL(-1)
DRT2-OD08C(-1)
DRT2-OD08CL(-1)
DRT2-WD16CL(-1)
DRT2-MD16CL(-1)
Errors occurring in
Slaves with inputs
DRT2-ID08(-1)
DRT2-ID16(-1)
DRT2-MD16(-1)
DRT2-MD16S(-1)
DRT2-ID16TA(-1)
DRT2-MD16TA(-1)
DRT2-ID16ML(X)(-1)
DRT2-ID32ML(-1)
DRT2-MD32ML(-1)
DRT2-ID32B/BV(-1)
DRT2-MD32B/BV(-1)
DRT2-ID16SL/SLH(-1)
DRT2-ID32SL/SLH(-1)
DRT2-MD32SL/SLH(-1)
DRT2-HD16C(-1)
DRT2-ID08C(-1)
DRT2-ID04CL(-1)
DRT2-ID08CL(-1)
DRT2-HD16CL(-1)
DRT2-MD16CL(-1)
Errors occurring in
Slaves equipped with
the Sensor Discon-
nected Detection func-
tion
DRT2-HD16C(-1)
DRT2-ID08C(-1)
DRT2-ID16SLH(-1)
DRT2-ID32SLH(-1)
DRT2-MD32SLH
(-1)
Errors occurring in
Slaves equipped with
the external load short-
circuit detection function
DRT2-OD08C(-1)
DRT2-MD16S(-1)
DRT2-OD16SLH(-1)
Model
The outputs cannot be held
when a communications error
has occurred.
The outputs cannot be cleared
when a communications error
has occurred.
There is a delay in the input’s
ON or OFF timing.
The Sensor Disconnected (Off-
wire) Detection Flag is going
ON for inputs that are not being
used.
A short-circuit was corrected
after being detected by the
external load short-circuit
detection function, but the Load
Shorted Flag does not go OFF.
Details
The Slave’s Output Hold/Clear
setting is set to clear outputs
when there is a communica-
tions error.
The Slave’s Output Hold/Clear
setting is set to hold outputs
when there is a communica-
tions error.
An input delay may be set in
the input filter function.
The Sensor Disconnected
Detection function (Off-wire
Detection function) may not
be disabled for the inputs that
are not being used.
The function is set for manual
reset. (The default setting is
manual reset.)
Probable cause
Set the Slave’s Output Hold/
Clear setting to hold outputs
when there is a communica-
tions error.
Set the Slave’s Output Hold/
Clear setting to clear outputs
when there is a communica-
tions error.
Either set the input filter value
to 0 or an appropriate non-
zero input filter value.
Disable the Sensor Discon-
nected Detection function
(Off-wire Detection function)
for inputs that are not being
used.
After correcting the short-cir-
cuit, turn the I/O power supply
OFF and then ON again.
Remedy
Section 9-2