DRT2-ID32BV-1 Omron, DRT2-ID32BV-1 Datasheet - Page 83

no-image

DRT2-ID32BV-1

Manufacturer Part Number
DRT2-ID32BV-1
Description
32 In Vert MIL Connector PNP
Manufacturer
Omron
Datasheet

Specifications of DRT2-ID32BV-1

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Functions of General-purpose Slaves and Environment-resistive Slaves
Checking Using the
DeviceNet
Configurator
4-3-2
Function Overview
ON Response Time
(Variable from 0 to 100 ms)
62
Input Filter
1,2,3...
Note The value for detecting a low voltage for the I/O power cannot be set.
The method used to check information from the DeviceNet Configurator (Ver.
2.20 or later) is described here.
1. Turn ON the power to the DRT2-series Smart Slave.
2. From the Maintenance Mode Window, double-click the icon of the applica-
Input values can be read several times during a set interval so that the input
value is enabled only when the value of all samples are the same. The input
filter is applied to all of the inputs of the Unit.
When input data changes to ON, the input data is read four times for the
period of the set interval (1/4 of 0 to 100 ms). If all values are ON, the input is
turned ON. The ON timing is delayed according to the length of the ON
response time.
The input filter can also be used to perform an ON delay operation (a delay for
the ON response time is created when the input filter is enabled).
Input data
ON
OFF
ON
OFF
ble DRT2-series Smart Slave in the Network Configuration Window to dis-
play the Maintenance Information Window. The I/O power is not being
supplied if the Input Power Supply Error or Output Power Supply Error
items are selected.
ON
1
OFF
2
OFF
3
ON
4
Not all values are
ON during the four
samples, so the
input is regarded as
being OFF.
Input data
ON
OFF
OFF
ON
ON delay time
(= input filter time)
ON
1
ON
2
ON
3
ON
4
All values are ON
during the four
samples, so the input is
regarded as being ON.
Section 4-3

Related parts for DRT2-ID32BV-1