Specifications of DRT2-ID32BV-1

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Setting Hysteresis
OFF Delay
Setting Using the DeviceNet Configurator
Analog Input Terminals
1,2,3...
The Comparator Result Flag turns OFF when the value is lower than the hys-
teresis width (H or HH alarm occurs) or exceeds it (L or LL alarm occurs), as
shown in the following diagram. If the analog value fluctuates around the
threshold, and the flag repeatedly turns ON or OFF, setting hysteresis will sta-
bilize the flag operation.
The time until the Comparator Result Flag turns OFF can be extended. For
example, even if the Flag is ON momentarily, the OFF delay can be set so that
the Master can receive notification of the Flag’s status.
1. Double-click the icon of the Analog Slave to be set in the Main Window and
HH Alarm Flag
HH Alarm Flag or
H Alarm Flag
HH set value
HH set value or
H set value
open the Edit Device Parameters Window. (From the Maintenance Mode
Window, click the right mouse button over the Slave icon and select Pa-
rameters and Edit.)
LL set value or L
set value
Hysteresis width
LL Alarm Flag or
L Alarm Flag
Hysteresis width
OFF delay
Section 7-4
Hysteresis
width
349