CJ1W-NC234 Omron, CJ1W-NC234 Datasheet - Page 214

no-image

CJ1W-NC234

Manufacturer Part Number
CJ1W-NC234
Description
High Speed Pulse Train 2 Axes
Manufacturer
Omron
Datasheet

Specifications of CJ1W-NC234

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
5
5-4 Memory Operation Parameter
5-53
Memory Operation Parameters List
Configuration Axis
Configuration
Axis
Parameter
name
4 sets of memory operation parameters are available for tasks 1 to 4. Set the parameters
according to the number of tasks which you use.
The explanation below is based on 1 task.
Select the configuration axis or axes of the task.
Configuration axis setting becomes valid at power supply ON, restart, or setup.
Configuration axis
Teaching setting
Interpolation axis stop
method
Error between axes
monitor setting
You cannot set an axis which is already in use for other task.
Precautions for Correct Use
General name
Select the configuration axis or axes of the task.
Bits 00 to 03 correspond to axes 1 to 4, respectively.
000 hex: Not use this task
0001 hex: Use axis 1 only
0003 hex: Use axes 1 and 2
0005 hex: Use axes 1 and 3
0007 hex: Use axes 1 to 3
0009 hex: Use axes 1 and 4
000B hex: Use axes 1, 2 and 4
000D hex: Use axes 1, 3 and 4
000F hex: Use axes 1 to 4
0: Not use as configuration axis
1: Use as configuration axis
Configuration Axis
Teaching Object
Interpolation Axis Stop Method
Error Between Axes Monitor Enable
Error Between Axes Limit Value
Error Between Axes Monitor Target Axis
CJ Position Control Units OPERATION MANUAL (CJ1W-NC214/234/414/434)
Function
Parameter name
0002 hex: Use axis 2 only
0004 hex: Use axis 3 only
0006 hex: Use axes 2 and 3
0008 hex: Use axis 4 only
000A hex: Use axes 2 and 4
000C hex: Use axes 3 and 4
000E hex: Use axes 2 to 4
000F hex
Reference
Setting
0000 to
range
page
5-53
5-54
5-54
5-55
Unit
At power supply
At power supply
Valid timing
ON, restart or
ON, restart or
Always
Always
setup
setup
Default
values
0

Related parts for CJ1W-NC234