CJ Position Control Units OPERATION MANUAL (CJ1W-NC214/234/414/434)
High-speed PTP start condition
Absolute movement received
/Relative movement received
Axis busy
Positioning operation
Pulse output
Operand
C
S
W
completed
You can only start 1 axis with 1 IOWR instruction.
Also note that only absolute movement and relative movement can be used for the positioning
functions that you can execute, and you cannot specify interrupt feeding.
instruction in each cycle until the Condition Flags [= Flag] turn ON.
instruction.
The PCU begins to output the pulses at the execution of high-speed PTP start. However, the change
of the axis status is reflected in the axis status memory area at the next I/O refresh.
To execute multiple high-speed PTP start, design a self-holding circuit that executes an IOWR
If high-speed PTP start is executed continuously, 0.5 ms is required to process the IOWR
Precautions for Correct Use
Description
Control data
Rightmost word number of
transfer source
Destination unit number and
number of transfer words
I/O refresh
IOWR
instruction
I/O refresh
Setting
This is a high-speed PTP command.
Absolute movement: 80xx hex
Relative movement: 81xx hex
(xx = 01 to 04 hex: Axes 1 to 4)
Specify the first word in [Direct Operation Command
Memory Area] for the axis for which you want to execute
high-speed PTP start.
Axis 1: B
Axis 2: B+12
Axis 3: B+24
Axis 4: B+36
For the beginning word in [Direct Operation Command
Memory Area], refer to"Direct Operation Command
Memory Area" on page 5-64.
W: Set the destination unit number.
Specify a unit number between 0 and 94 in the decimal
&0 to 94 or in the hex #0000 to 005E.
W+1: Set the number of transfer words.
Set the number of words in [Direct Operation Command
Memory Area]. This value is fixed to #000C.
The Absolute movement received bit
and the relative movement received bit
in the axis status memory area will not
turn on at the execution of high-speed PTP start.
Time
6-5 High-speed PTP Start