CJ1W-NC414 Omron, CJ1W-NC414 Datasheet - Page 10

no-image

CJ1W-NC414

Manufacturer Part Number
CJ1W-NC414
Description
High Speed Pulse Train 4 Axes
Manufacturer
Omron
Datasheet

Specifications of CJ1W-NC414

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Precautions
8
6. Conformance to EC Directives
Applicable Directives
Concepts
Note
Conformance to EC Directives
1,2,3...
Installation within Control Panel
• EMC Directives
Applicable EMC (Electromagnetic Compatibility) standards are as follows:
EMS (Electromagnetic Susceptibility):
EMI (Electromagnetic Interference):
EMC Directives
OMRON devices that comply with EC Directives also conform to the related EMC
standards so that they can be more easily built into other devices or machines. The actual
products have been checked for conformity to EMC standards (see the following note).
Whether the products conform to the standards in the system used by the customer,
however, must be checked by the customer.
EMC-related performance of the OMRON devices that comply with EC Directives will
vary depending on the configuration, wiring, and other conditions of the equipment or
control panel in which the OMRON devices are installed.
The customer must, therefore, perform final checks to confirm that devices and the
overall machine conform to EMC standards.
The PCUs comply with EC Directives. To ensure that the machine or device in which a
PCU is used complies with EC Directives, the PCU must be installed as follows:
1. The PCU must be installed within a control panel.
2. Reinforced insulation or double insulation must be used for the DC power supplies
3. PCUs complying with EC Directives also conform to the Common Emission Standard
Unnecessary clearance in cable inlet or outlet ports, operation panel mounting holes, or
in the control panel door may cause electromagnetic wave leakage or interference. In this
case, the product may fail to meet EC Directives. In order to prevent such interference,
fill clearances in the control panel with conductive packing. (In places where conductive
packing comes in contact with the control panel, ensure electrical conductivity by
removing the paint coating or masking these parts when painting.)
used for the communications and I/O power supplies.
(EN61000-6-4). With regard to the radiated emission (10-m regulations),
countermeasures will vary depending on the devices connected to the control panel,
wiring, the configuration of the system, and other conditions. The customer must,
therefore, perform final checks to confirm that devices and the overall machine
conform to EC Directives.
CJ Position Control Units OPERATION MANUAL (CJ1W-NC214/234/414/434)
EN61000-6-2
EN61000-6-4
(Radiated emission: 10-m regulations)

Related parts for CJ1W-NC414