CJ Position Control Units OPERATION MANUAL (CJ1W-NC214/234/414/434)
Memory Area Allocation List
Special I/O Unit Memory Area
Special I/O Unit Memory areas are allocated in the CPU Unit according to the specified unit
number.
The CJ1W-NC214/NC234/NC414/NC434 occupy 18 word as a Unit Control Memory area.
number
The CJ1W-NC214/NC234/NC414/NC434 occupy the above areas for 2 units. Since they occupy
the area next to the one for the unit number you set, set each unit number so that area duplication
does not occur with other Special Units.
Since the CJ1W-NC214/NC234/NC414/434 are occupied areas for 2 units, you cannot set them
to No. 95.
Do not set the same unit number or Special I/O Unit memory area which is already in use by other
Special I/O Unit. If you set a duplicate unit number or area, the fatal error "Unit number duplication
error" occurs and the operation stops.
Operation Command Memory areas and Memory Operation Command Memory areas, in addition
to Unit Control Memory areas. For details, refer to "Operating Memory Area" on page 5-56.
To perform axis control, direct operation or memory operation, you also need to set Direct
No. 93
No. 94
No. 95
No. 0
No. 1
No. 2
No. 3
Unit
Precautions for Correct Use
:
CJ1W-NC214/NC234/NC414/NC434
Setting not possible
2000 to 2019
2010 to 2029
2020 to 2039
2030 to 2049
2930 to 2949
2940 to 2959
:
2-1 Name of Each Part and Area Allocation
2-4