CJ Position Control Units OPERATION MANUAL (CJ1W-NC214/234/414/434)
RUN ERC ERH SYNC X
LED
Y
Z
U
PCU Type Error
Out-of-range Unit
Number
PLC Initial
Processing Error
System Software
Error
Memory Error
Synchronous
Operation Cycle
Invalid
Synchronous Time
Monitor Timeout
Synchronous Data
Receive Error
PLC Watchdog
Timer Error
Bus Error
CPU Unit Monitor
Error
CPU Unit Stop
Error
Error name
The PCU is not recognized
correctly.
The PCU unit number is
outside the specified range.
The initialization process in
the CPU Unit was not
successful.
An error in the PCU internal
system ROM.
An error in the PCU internal
memory.
The synchronization control
period exceeds the range
usable by the PCU.
The timing of synchronous
control period can not be
obtained properly.
Data exchange by
synchronous data link could
not be executed properly.
The CPU Unit system is not
operating properly.
An error in PLC bus operation.
Processes are not executed
properly due to an overload of
the CPU Unit.
An error that stops the CPU
Unit occurred.
Cause
12-3 LED Error Indicator
Reconnect the power supply
or restart the PCU. If this error
occurs again, replace the
PCU.
Change the unit number to a
value inside the settable
range, and then reconnect the
power supply.
Reconnect the power supply
or restart the PCU. If this error
occurs again, replace the
PCU.
Reconnect the power supply
or restart the PCU. If this error
occurs again, replace the
PCU.
Set a synchronization cycle
time set value within the
settable range and then
reconnect the power supply.
Check the installed condition
of the PCU and then
reconnect the power supply or
restart the PCU. If this error
occurs again, replace the
PCU.
If this error occurs, the PCU
stops all axes immediately.
Check the installed condition
of the PCU and synchronous
unit control setting, and then
execute an error reset. If this
error occurs again, replace the
PCU.
If this error occurs, the PCU
decelerates the applicable
axis to a stop.
Reconnect the power supply
or restart the PCU. If this error
occurs again, replace the
PCU.
If this error occurs, the PCU
cuts off all outputs.
Check the operating condition
of the CPU Unit.
Remove the cause that
stopped the CPU Unit.
If this error occurs, the PCU
cuts off all outputs.
Remedy
12-12