R88M-WP10030S-BWS1 Omron, R88M-WP10030S-BWS1 Datasheet - Page 223

no-image

R88M-WP10030S-BWS1

Manufacturer Part Number
R88M-WP10030S-BWS1
Description
SERVO MOTOR 100W 100V W/BRAKE
Manufacturer
Omron
Datasheet

Specifications of R88M-WP10030S-BWS1

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Other names
R88MWP10030SBWS1
System Design and Installation
• Use ground lines with a minimum thickness of 3.5 mm
• If no-fuse breakers are installed at the top and the power supply line is wired from the lower duct, use
• No-fuse breakers, surge absorbers, and noise filters should be positioned near the input terminal
• Wire the noise filter as shown at the left in the following illustration. The noise filter should be installed
• Use twisted-pair cables for the power supply cables whenever possible, or bind the cables.
• Separate power supply cables and signal cables when wiring.
H Control Box Structure
D Case Structure
• Construct the control box case of metal, and weld the joints between the top, bottom, and sides so that
• For assembly, strip the paint off of joined areas (or mask them during painting), to make them electri-
• If gaps are opened in the control box case when tightening down screws, make adjustments to prevent
• Do not leave any conducting part unconnected.
are as short as possible.
metal tubes for wiring and make sure that there is adequate distance between the input lines and the
internal wiring. If input and output lines are wired together, noise resistance will decrease.
block (ground plate), and I/O lines should be isolated and wired using the shortest distance possible.
at the entrance to the control box whenever possible.
they will be electrically conductive.
cally conductive.
this from occurring.
If there are gaps in the control box from cable openings, operating panel installation
holes, gaps around the door, and so on, it may allow electric waves to penetrate. In order
to prevent this from occurring, take the measures described below.
Correct: Separate input and output
Correct: Properly twisted
AC input
Ground
Driver
AC output
or
2
, and arrange the wiring so that the ground lines
WRONG: Noise not filtered effectively
AC output
AC input
Binding
Ground
Correct: Cables are bound.
Driver
Chapter 3
3-29

Related parts for R88M-WP10030S-BWS1